SD700SP 

POWER ELECTRONICS 

 

14 

TECHNICAL CHARACTERISTICS 

 

 

TECHNICAL CHARACTERISTICS 

 
 
The following table is for a standard SD700SP. Consult the technical brochure or Power Electronics for 
further information.  

INPUT

 

Power range 

1,5kw - 560kw 

[1]

 

Voltage power 

380-500vac, 3 phases (±10%) 540-900vdc (830vdc for Frame 1 & 2) 

Hybrid supply 

Yes, simultaneous connection 

Input frequency 

50hz/60Hz ± 6% 

Input rectifier technology 

Thyristor-diode 

DPF=cos phi / Power factor 

≥ 0.98 / ≥ 0.91

 

EMC input filter 

Frames 1 & 2: First environment (C2 Standard); Frames 3 to 8: second 

environment (Industrial) (C3 Standard); first environment (C2 Optional). 
C1 consult Power Electronics. Optional IT filter. 

Current THDI (%) / Filter 

harmonics 

≤ 40% / 

Choke coils 3% impedance 

Regenerative 

No 

 

 

 

OUTPUT

 

Output frequency 

[2]

 

0...200hz 

Overload capacity 

Constant torque/heavy duty: 150% during 60 sec at 50°c 

Efficiency @rated current and 
voltage) 

≥ 98%

 

Switching frequency 

4 to 8kHz - PEWave 

Output dv/dt filter 

500 to 800V/ms 

[3]

 

Output cable length 

[4]

 

USC 300m, SC 150m 

 

 

 

ENIRONMENTAL 
CONDITIONS

 

Operation temp. / storage temp. 

-20°C to +50°C / -40°C to +70°C 

Altitude/power altitude derating 

[1]

  1000m / >1000m, 1% Pn(kW) per 100m; 4000m maximum 

Ambient humidity 

<95%, non-condensing 

Degree of protection 

IP20, IP54 

 

 

 

INPUTS / OUTPUTS 

Digital inputs 

6 Programmable active high (24vdc), Isolated power supply, 1 PTC input 

Digital outputs 

3 Programmable changeover relays (250vac, 8a or 30Vdc, 8a) 

Analogue input 

2 Programmable differential inputs: 0 - 20ma, 4 - 20ma, 0 - 10Vdc and 

±10Vdc. (optically isolated) 

Analogue outputs 

2 Isolated programmable outputs: 0 - 20ma, 4 - 20ma, 0 - 10Vdc and 
±10Vdc 

Encoder inputs (optional) 

2 Differential encoders input. voltages inputs from 5 to 24Vdc 

User power supply 

+24Vdc user power supply (max. 180mA) regulated and short-circuit 

protected. 
+10Vdc user power supply (max. 2 potentiometers r= 1 k

) regulated 

and short-circuit protected 

I/O Extension board (optional) 

4 Digital Inputs: Programmable inputs and active high (24Vdc). optically 

isolated. 
1 Analogue Input: Programmable and differential input. 

5 Digital Outputs: Programmable multi-function relays. 
1 Analogue Output: Programmable outputs in voltage / current. 

External power supply (optional) 

24V External Power Supply, Fault Relay integrated 

 

 

 

COMMUNICATION

 

Standard protocol 

Modbus-RTU 

Optional protocol 

Profibus-DP, Devicenet, Ethernet (Modbus TCP), Ethernet IP, CAN open, 

N2 Metasys Gateway 

 

 

 

OUTPUT

 

Certifications 

CE, cTick, UL 

[5]

, CUL 

[5]

, GL

[6]

 

Electromagnetic compatibility 

EMC directive (2004/108/CE), IEC/EN 61800-3 

Design and construction 

LVD directive (2006/95/CE), IEC/EN 61800-2, IEC/EN 61800-5-1, IEC/EN 
60146-1-1, IEC60068-2-6, IEC/EN 61800-5-2(sto) TÜV Rheinland 

Certified 

[1] For other configuration, consult Power Electronics. 
[2] For operation frequencies higher than 100Hz, consult Power Electronics. 

[3] Valid for frames 3 to 8, depending on the rated power, the input voltage and under Power Electronics' installation recommendations. For 
Frames 1 and 2, optional filters are available. 

[4] SC: Shielded cable, USC: Unshielded Cable. Follow Power Electronics installation recommendations. For greater cable lengths and first 
environment (C2) consult Power Electronics. 

[5] On certification process. 
[6] SD700 series from frame 5 on.

 

 

Содержание SD700SP Series

Страница 1: ...SD700SP VARIABLE SPEED DRIVE FOR SOLAR PUMPING HARDWARE AND INSTALLATION MANUAL www power electronics com...

Страница 2: ......

Страница 3: ...Variable Speed Drive for Solar Pumping Hardware and Installation Manual Edition December 2017 SD7SPMTHW02AI Rev A...

Страница 4: ...reserves the right to modify all or part of the contents of this manual without previous notice To consult the most updated information of this product you may access our website www power electronic...

Страница 5: ...d Storage 17 Handling and Transportation 17 MECHANICAL INSTALLATION 20 Environmental ratings 20 Drive mounting 21 Clearances 22 Cooling 22 POWER CONNECTION 25 AC configuration 25 DC configuration 26 T...

Страница 6: ...SD700SP POWER ELECTRONICS 4 TABLE OF CONTENTS MAINTENANCE 54 Warnings 54 Routine Inspection 54 CE MARKING 56 EMC Directive 56 Low Voltage Directive 56...

Страница 7: ...tions to avoid the risk of electrical shocks CAUTION Identifies potentially hazardous situations which if not avoided could result in product damage or minor or moderate personal injury Read the messa...

Страница 8: ...he cover except for periodic inspections or wiring even if the input power is not applied Otherwise you may access to the charged circuits and may get an electric shock Wiring and periodic inspections...

Страница 9: ...eld the cabinet this can damage the electronic sensitive equipment inside NOTICE RECEPTION The SD700SP are carefully tested and perfectly packed before delivering In the event of transport damage plea...

Страница 10: ...S 902 40 20 70 34 96 136 65 57 or your nearest agent Wear safety glasses when operating the drive with power applied or the front cover is removed Handle and transport the drive following the recommen...

Страница 11: ...and spare parts without Power Electronics supervision Before programming or operating the SD700SP Series initialise all parameters back to factory default values CAPACITORS DEPLETION If the drive has...

Страница 12: ...her the solar PV panels off grid or simultaneously from the PV panels and grid supply PV solar assisted The SD700SP is a compact fully factory approved solution which leads to easy installation and co...

Страница 13: ...takes all energy possible from the PV field to pump the water needed and if the energy of PV field is not enough SD700SP switches on the AC input to top up and deliver all energy required by the motor...

Страница 14: ...the motor operation frequency range typically from 30Hz to 45Hz which generates a minimum pump flow At the same time the frequency range determines the minimum power threshold and therefore PV sizing...

Страница 15: ...tact our sales representatives Standard Ratings 400Vac 565Vdc FRAME CODE Operation Temperature 50 C AC SUPPLY DC SUPPLY 565Vdc I A Rated Motor Power kW at 400VAC 150 Overload A I A DC input I A DC inp...

Страница 16: ...solated Analogue outputs 2 Isolated programmable outputs 0 20ma 4 20ma 0 10Vdc and 10Vdc Encoder inputs optional 2 Differential encoders input voltages inputs from 5 to 24Vdc User power supply 24Vdc u...

Страница 17: ...hotovoltaic solar field design is necessary knowing the minimum and maximum continuous DC input voltages we can supply the SD700SP Maximum DC Voltage Minimum DC voltage Voc 850VDC Frames 1 2 Voc 900VD...

Страница 18: ...Depth D 1 508 190 279 15 2 510 296 329 26 3 854 300 358 67 5 4 1245 320 439 94 5 1712 431 529 200 6 1712 786 529 335 7 1712 1132 529 479 8 1712 1482 529 585 SD700SP Frame 1 SD700SP Frame 7 SD700SP Di...

Страница 19: ...elivery notes are permissible Any other transport method or system could damage the unit The SD700SP without solar kit is delivered horizontally Frames 1 and 2 are delivered in a cardboard box and fra...

Страница 20: ...irement it could cause damage to the equipment and lead to injury to people To unpack if necessary unscrew the bolts that fix the wooden box with the pallet Then the drive is fixed to the pallet throu...

Страница 21: ...on the floor stop lowering it just before reaching the floor and then slowly lower it on the floor to avoid any shock During handling and transportation the goods should not be exposed to moisture ove...

Страница 22: ...nvironmental ratings are the following ones Environmental category Indoor Wet locations No Pollution degree PD3 Ingress protection rating Clean zone Electronics IP54 or IP20 Power connection and Input...

Страница 23: ...chorages placed on the rear part of the drive which supports the VFD s weight and the possible forces generated by the wiring SD700SP without solar kit wall mounted Stand alone drives Frames 5 to 8 ar...

Страница 24: ...e may suffer from overheating To ensure a suitable cooling avoid the recirculation of air and keep the minimum clearance distances indicated below Minimum clearances for frames 1 to 4 SD700SP without...

Страница 25: ...ternal forced convection system 2nd Area Rectifier bridge Inverter bridge and DC bus cooling area The drive integrates axial fans that intake the air from the bottom part of the drive and evacuates it...

Страница 26: ...3 OPERATION FLOW m3 h C 180 360 720 1080 INLET GRATING NET SECTION m2 B 0 081 0 016 0 025 0 031 0 034 0 041 0 041 Valid table for the SD700SP without the solar kit Heat dissipation The heat generated...

Страница 27: ...are available for TT grids For other grids consult with Power Electronics Check the serial number to ensure the correct drive selection External line side protection Select fuses and switches in acco...

Страница 28: ...lectrical equipment from over voltages On load Breaker To be able to open the circuit while the load on the system is connected Fuses To provide overcurrent protection the equipment Blocking diode To...

Страница 29: ...motor as a motor relay does The SD700SP includes a power and a control board to control the rectifier thyristor diode s bridge shooting the inverter IGBT s bridge shooting the soft charge the DC bus...

Страница 30: ...SD700SP POWER ELECTRONICS 28 POWER CONNECTION SD700SP frames 1 and 2 power electronics SD700SP frames 3 and 4 power electronics SD700SP frames 5 to 8 power electronics...

Страница 31: ...tput busbars are labelled according to the following diagram The AC input terminals L1 L2 L3 and PE AC drive supply output terminals U V W and PE motor supply and the DC input terminals HVDC HVDC must...

Страница 32: ...oltage Use copper or aluminium 1 KV conductors suitable for solar installations The recommended cable types and lengths between the drive at factory settings and the motor are Unshielded cable 300m As...

Страница 33: ...e in force in those countries or areas where this device is going to be installed Do not use capacitors for power factor correction surge suppressors or RFI filters on the output side of the drive Doi...

Страница 34: ...per phase could be found in the Power connection terminals section Recommended Cable Section for 400VAC The DC conductors will depend on the photovoltaic installation design The installation must be...

Страница 35: ...ed to the drive In other words connect the motor s ground conductor to the PE output terminal of the drive and not to the installation s ground We recommend that the cross section of the motor s groun...

Страница 36: ...ystem PDS are defined in IEC EN 61800 3 standard that is included in the Declaration of conformity CE enclosed In European Union EN61800 3 standard takes precedence over all generic or previously appl...

Страница 37: ...speed drive could be installed in residential areas first environment by employing optional RFI filters that permits to achieve compliance with C2 category SD700SP is not a retail unit which is neithe...

Страница 38: ...is recommended for control signals to use shielded cable and to follow recommendations included in section Wiring recommendations CAUTION Select communication and control system according to the driv...

Страница 39: ...s The response threshold can be set from 0 to 30 of the rated current G 11 3 For further information see Programming and Software Manual This function is not intended to work as a personnel safety or...

Страница 40: ...Safe Torque Off STO allows the drive output to be disabled so that the drive cannot provide power or generate torque in the motor The STO safety function has been certified by T v Rheinland according...

Страница 41: ...POWER ELECTRONICS SD700SP POWER CONNECTION 39 EN Power terminals Connections for Frame 1 Connections for Frame 2...

Страница 42: ...SD700SP POWER ELECTRONICS 40 POWER CONNECTION Connections for Frame 3 Connections for Frame 4...

Страница 43: ...POWER ELECTRONICS SD700SP POWER CONNECTION 41 EN Connections for Frame 5...

Страница 44: ...SD700SP POWER ELECTRONICS 42 POWER CONNECTION Connections for Frame 6...

Страница 45: ...POWER ELECTRONICS SD700SP POWER CONNECTION 43 EN Connections for Frame 7...

Страница 46: ...SD700SP POWER ELECTRONICS 44 POWER CONNECTION Connections for Frame 8...

Страница 47: ...rol board EMC shield clamps that ensure a 360 effective shield bonding Digital signal cables must be grounded at both ends of the cable It is recommended to use independent shielded cables for digital...

Страница 48: ...ctric shock The user will have only access to the inverter control board that is equipped with the user interface ports and connectors It integrates as standard PTC connection analogue inputs and outp...

Страница 49: ...l generator group state Terminals 10 and 11 AI1 Radiation sensor Terminals 12 and 13 AI2 Pressure transducer Only with pressure control Terminals 29 and 30 Starting the generator set only for Hybrid m...

Страница 50: ...SD700SP POWER ELECTRONICS 48 CONTROL CONNECTION The following figure provides an overview of the standard wiring of control terminals through the X1 and X2 user connectors for the standard SD700...

Страница 51: ...d JP1101 JP1104 Communications ports are clearly indicated in that connector Put the jumper in the desired position according to your needs Jumper for communications port selection Modbus communicatio...

Страница 52: ...tial Input signal level 1 logical 5V differential 0 logical 5V differential Insulation 50VDC regarding to the earth Programmable inputs via Modbus 7 digital inputs 2 programmable analogue inputs 0 10V...

Страница 53: ...ICS SD700SP MODBUS COMMUNICATION 51 EN RS232 Connections The following diagram shows a common wiring for a RS232 connection RS485 Connections The following diagram shows a common wiring for a RS232 co...

Страница 54: ...e the photovoltaic installation has been done according to the project Check the photovoltaic panel data sheet behind the panel Check how many series and how many panels in each series there are Check...

Страница 55: ...that the display is turned on and set the drive control parameters Follow the instruction delivered in Software and Programming manual Check line voltages displayed Start the drive without motor using...

Страница 56: ...e Installation site conditions Drive cooling system conditions Excessive vibrations or noise in the motor Excessive overheating Normal output current value on the monitor Inspection site Inspection el...

Страница 57: ...overheated point o o Visual check Measure the surface and connectors temperature No anomaly Check that the temperature is homogeneous and below 70 C Infrared thermometer Contactor Is there any contact...

Страница 58: ...irective defines the requirements for immunity and emissions of electrical equipment used within the European Union SD700SP Series drives are in accordance with the directive IEC 61800 3 2004 about ad...

Страница 59: ...DECLARATION OF CONFORMITY CE DECLARACI N DE CONFORMIDAD CE References of the harmonized technical norms applied under the Machinery Directive...

Страница 60: ...24h Technical Assistance 365 days a year Find your nearest delegation http power electronics com contact Follow us on...

Страница 61: ...SD700SP VARIADOR DE VELOCIDAD DE BAJA TENSI N MANUAL DE APLICACI N BOMBEO SOLAR www power electronics com...

Отзывы: