Operation: APT1200-12
Power on:
On the LED control “Inverter” lighting - Green LED.
AC Mode:
On the LED control “AC Mode” lighting - Green LED.
Fault:
One the LED control “Fault” lighting-Red LED.
Troubleshooting
PROBLEM: No Input Voltage
Reason
Solution
Poor contact with battery
terminals.
Shut down inverter and disconnect.
Clean terminals thoroughly and
reconnect.
Blown DC battery fuse(s).
Turn off inverter. Fix problem. Replace
fuse(s) with same type and rating.
PROBLEM: Inverter is Shut Down
Reason
Solution
Battery voltage below 10 Volts.
Charge or replace battery.
Inverter is too hot (thermal shut
down mode).
Allow inverter to cool. Check for
adequate ventilation. Re-duce the
load on the inverter to rated
continuous power.
Unit may be defective.
See warranty and call customer
service.