Cabling
n
The cabling must be in line groups (high voltage, current supply,
signal and data lines)
n
High voltage lines and signal respectively data lines must be laid in
separate channels or bundles
n
The signal and data lines have to be routed as near as possible
beside ground areas
Reference potential and ground of all electrical operating supplies
n
Installation parts and cabinets with your CNC control unit have to
be connected in star topology with the isolation/protected ground
conductor system to avoid ground loops.
n
Sufficiently dimensioned potential compensation lines have to be
laid if there are potential differences between installation parts and
cabinets
Area-wide grounding of the inactive metal parts
n
A central connection between the ground and the protected ground
conductor system have to be installed.
n
All inactive metals have to be connected extensively and impe-
dance-low.
Fixing of the cable shield
n
Data cables and analog cables must be laid separately from each
other.
n
The cable shield has to be laid extensively on a protected ground
conductor rail directly after the cabinet entry and the fixation of the
shield with cable clamps.
n
The isolation / protected ground rail has to be connected impe-
dance-low with the cabinet.
n
The metallic or metallized plug cases for shielded cables must be
used.
n
When transmitting signals with small amplitudes the one sided
grounding of the cable shield may be favorable.
Electromagnetic interferences may interfere with the control unit:
n
Electromagnetic fields (RF coupling)
n
Magnetic fields with power frequency
n
Power supply
n
Protected ground conductor
n
Superbus system
Depending on the spreading medium and the distance to the interfer-
ence cause, interferences to the control unit occur by means of capaci-
tive, galvanic, inductive or radiant coupling mechanisms.
Important Rules For EMC
Possible Interferences
PA 8000 LW CNC control unit
Technical data
25.09.2015 | 89
Содержание PA 8000 LW Series
Страница 1: ...PA 8000 LW CNC control unit Installation instructions...
Страница 12: ...PA 8000 LW CNC control unit General information 25 09 2015 12...
Страница 27: ...3 Design and function 3 1 Overview Top View PA 8000 LW CNC control unit Design and function 25 09 2015 27...
Страница 85: ...4 4 Dimension sheet PA 8000 LW CNC control unit Technical data 25 09 2015 85...
Страница 86: ...Fig 54 dimension sheet PA 8000 LW CNC control unit Technical data 25 09 2015 86...
Страница 123: ...Fig 67 RMA Form RMA Form PA 8000 LW CNC control unit Service and return process 25 09 2015 123...
Страница 126: ...PA 8000 LW CNC control unit Dismounting and decommissioning 25 09 2015 126...
Страница 127: ...11 EC Declaration of Conformity PA 8000 LW CNC control unit EC Declaration of Conformity 25 09 2015 127...
Страница 128: ...Fig 68 EC Declaration of Conformity PA 8000 LW CNC control unit EC Declaration of Conformity 25 09 2015 128...
Страница 130: ...PA 8000 LW CNC control unit Proof of change 25 09 2015 130...