Operation
Front Panel Controls and LCD Indicators
Shown below are the controls and indicator lights on the front of
Invisimo
.
5
6
7
8
9
10 11
0% 25% 50% 75% 100%
4
1
2 3
1. Power On: Please make sure the battery connection before you turn on the
Invisimo
2. UPS Off
3. Charger Only
4. UPS Test Switch
:
When UPS is working under AC mode,it also activates the UPS’s
self-test by press the bottom.
5. Line-On: AC Normal
6. O-Temp. : If the UPS is over temperature, the light will turn on and the alarm will sound
continuously.
7. Back-Up: Battery in back-up
8. Over Load: If the UPS is overloaded, the light will turn on and the alarm will sound
continuously
9. UPS Cut-Off: Overload or Cut-off
10. Battery Level: A bar graph showing how much of the UPS battery is being used.
11. Load Level: A bar graph showing how much of the UPS power is being used.
Back Panel Description
Shown below are the components on the back of
Invisimo
.
3
1
4
2
1
5
5
1. Input Breaker
2. AC Input Connector
3. Output Receptacle(s)
4. DC Input Connector (Battery Terminal)
5. Output Breaker
Battery Connection
Step 1.
Connect to 12V(24V) battery. “+” is positive, “-“ is negative. Reverse polarity
connection will blow internal fuse and may damage inverter permanently.(See
Specification)
Step 2.
DC to AC inverters require high amperage / low voltage DC power to low amperage /
high voltage AC power. To operate properly connect inverter DC input terminals
direct to battery with heaviest wire available, see chart below:
Model
DC Input Voltage Max. Watts Out Approx. Amps Req’d Wire Gauge
Invisimo
-700
12V 450W
65A
10AWG*2
Invisimo
-1000
12V 600W
85A
8AWG*2
Invisimo
-1500
12V 900W 125A
4AWG*2
Invisimo
-2000
24V 1200W
85A 8AWG*2
Invisimo
-3200
24V 2000W 140A
2AWG*2