Operation 

Front Panel Controls and LCD Indicators 

Shown below are the controls and indicator lights on the front of 

Invisimo

 

5

6

7

8

9

10 11

0% 25% 50% 75% 100%

4

1

2 3

 

 

1. Power On: Please make sure the battery connection before you turn on the 

Invisimo 

2. UPS Off 

3. Charger Only 

4. UPS Test Switch

:

When UPS is working under AC mode,it also activates the UPS’s

 

self-test by press the bottom. 

5. Line-On: AC Normal 

6. O-Temp. : If the UPS is over temperature, the light will turn on and the alarm will sound 

continuously. 

7. Back-Up: Battery in back-up 

8. Over Load: If the UPS is overloaded, the light will turn on and the alarm will sound 

continuously 

9. UPS Cut-Off: Overload or Cut-off 

10. Battery Level: A bar graph showing how much of the UPS battery is being used. 

11. Load Level: A bar graph showing how much of the UPS power is being used.

 

 

Back Panel Description 

Shown below are the components on the back of 

Invisimo

 

3

1

4

2

1

5

5

 

 

1. Input Breaker   

2. AC Input Connector 

3. Output Receptacle(s) 

4. DC Input Connector (Battery Terminal) 

5. Output Breaker 

Battery Connection 

Step 1.

 Connect to 12V(24V) battery. “+” is positive, “-“ is negative. Reverse polarity 

connection will blow internal fuse and may damage inverter permanently.(See 

Specification) 

Step 2.

 DC to AC inverters require high amperage / low voltage DC power to low amperage / 

high voltage AC power. To operate properly connect inverter DC input terminals 

direct to battery with heaviest wire available, see chart below: 

Model 

DC Input Voltage Max. Watts Out Approx. Amps Req’d Wire Gauge 

Invisimo

-700 

12V 450W 

65A 

10AWG*2 

Invisimo

-1000 

12V 600W 

85A 

8AWG*2 

Invisimo

-1500 

12V 900W  125A 

4AWG*2 

Invisimo

-2000 

24V 1200W 

85A 8AWG*2 

Invisimo

-3200 

24V 2000W  140A 

2AWG*2 