Operation
01.4IB.48080
2) Changing the Slave ID
a. Double click on the value for the slave
ID in the Modbus Poll window for the
holding register, the following dialogue
will appear shown in
.
Figure 11 Slave ID Change
b. Enter the desired slave ID in the box
labeled “value” and press the enter
key or click “send”. Connection to the
device will temporarily be lost until the
next steps in this process have been
performed.
c. Press the F8 key to open the Read/Write
.
Figure 12 Modbus Poll Read/Write Definition
d. Enter the new slave ID into the box
labeled “Slave ID” and press the enter
key or click “OK”. Connection will be
reestablished.
e. Repeat steps 3 and 4 for the Input
register window.