![Powell BriteSpot Plus Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/powell/britespot-plus/britespot-plus_instruction-bulletin_1585634045.webp)
Powered by Safety
®
35
Usage
01.4IB.48041
Figure 45 Alarm Configuration Web Page
By default, the BriteSpot®
Plus comes with alarm one
preconfigured. See
Configuration Web Page Settings
for
all default values.
Table K Alarm Configuration Web Page Settings
Parameter
Default Value
Range/Options
Alm 1
Alm 2-8
Type
Abs
Temp
Disabled
Disabled, Absolute
Temperature,
Absolute Current
Warning Off
85 °C
1
Any integer (°C or °F or A)
Note: Warning Off is the threshold for a warning condition to end.
Warning On
90 °C
2
Any integer (°C or °F or A)
Note: Warning On is the threshold for a warning condition to begin.
This parameter must be greater than the value that Warning Off
is set to.
Alarm Off
100 °C
3
Any integer (°C or °F or A)
Note: Alarm Off is the threshold for a warning condition to end.
This parameter must be greater than the value that Warning Off
is set to.
Alarm On
105 °C
4
Any integer (°C or °F or A)
Note: Alarm On is the threshold for a alarm condition to begin.
This parameter must be greater than both the value that Warning
On is set to as well as the value that Alarm Off is set to.
Latching
False
False
True/False
Sources
All
available
BriteSpot
sources
None
BriteSpot Channels 1-36
(when available)
MCS 1-8 (when available)
Содержание BriteSpot Plus
Страница 4: ...Powered by Safety 01 4IB 48041 BriteSpot Plus This page is left blank intentionally ...
Страница 29: ...Powered by Safety 19 Installation 01 4IB 48041 Figure 20 Panel Mount Clip Installation X X ...
Страница 57: ...Powered by Safety 47 Appendix A 01 4IB 48041 Figure 64 10250 BSPL 18C1P1E0X0 Dimensions ...
Страница 58: ...Powered by Safety 48 Appendix A 01 4IB 48041 BriteSpot Plus Figure 65 10251 BSPL 09C1P E0X0 Dimensions ...