Powered by Safety
®
18
Installation
01.4IB.48040C
BriteSpot™ BSG3
Figure 20 Safe Dielectric Routing Practices
30 cm
Note:
Ensure that at least 30 cm
(12") of fiber is suspended prior to
fastening.
4. Do not straddle phases with the fiber.
The fiber must go from the LOI to any
non-energized contact point and then to
the BriteSpot™ G3 Conversion Module.
5. Mark each end of the fiber with a means
to identify each fiber when finalizing the
installation. If this is not done, it can be
very challenging to correlate installation
location with the fiber. Black marker and
tape are acceptable, as are approved
wire markers (preferred). Ensure to make
all markings a safe distance from the
energized end, typically this is 60-100 cm
(2-3 ft).
d. m
Ount
g3 c
OnverSiOn
m
Odule
The G3 Conversion Module provides the
power, telemetry, and user interface to the
sensors. Once installed, the G3 Conversion
Module can be configured to provide a wide
range of features through the Ethernet and
serial ports. In addition to proximity to the LOI,
thought should also be given to ensuring that
there is access to the G3 Conversion Module
following installation. This is needed for initial
configuration and retrieval of onboard logged
data.
1) Mount DIN Rail
Attach a segment of 35 mm DIN rail to a
location where the BriteSpot G3 Conversion
Module will be secured. When selecting
a location for installation, ensure that the
ambient temperature will be below 70˚C
(158˚F). Approximately 13 cm (5”) of DIN
rail is needed for mounting the conversion
module. If other peripherals, such as DC
power supplies or MODBUS gateways
are also installed, consider increasing
the length of DIN Rail to accommodate
the extra items. Other items to consider
include leaving adequate room for the
fibers and wire connections to the module.
Approximately 100 mm (4 in) should be left
both above and below the center of the
DIN rail.
Содержание BriteSpot BSG3
Страница 1: ...Instruction Bulletin 01 4IB 48040C BriteSpot BSG3 Powered by Safety ...
Страница 4: ...Powered by Safety BriteSpot BSG3 01 4IB 48040C This page is intentionally left blank ...
Страница 10: ...Powered by Safety BriteSpot BSG3 01 4IB 48040C This page is intentionally left blank ...
Страница 37: ...Powered by Safety 27 Usage 01 4IB 48040C Figure 34 LCD Menu and Navigation ...