Powered by Safety
®
26
Specifications
Circuit Breaker Monitor
01.4IB.48070A
Table N Digital Voltage Input
Maximum Operating Voltages Range
+/-407VDC
Operating Characteristics
Wet/dry. Self-excited contact monitoring input
Isolation
2.5VAC for 1 minute
Leakage Current (when monitored contacts are
open)
Less than 250uA
Response Time
Less than 0.5ms
Applications
Monitoring: "52A" contact
"LCS" contact
Table O Internal Environment Monitoring
Measurement
CBM Internal Temperature
Temperature
-40°C to 85°C +/-2°C
Table P Hall Effect Sensor
Supply Voltage
5VDC
Measurement Range
Min +/-0.25A
Max +/- 20.0A
Measurement Resolution
0.05A
Measurement Accuracy
+/-5% of FSD
Operating Temperature Range
-40°C to 70°C
Table Q Optical Wireless Communication
Wavelength
850nm (Infrared)
Baud Rate
0.5Mbps
Range
24 inches with direct line of sight
Viewing Angle
30 degrees
Table R Fiber Optic Temperature Measurement
Monitoring
3 point temperature measurement using BriteSpot
®
G2.1 module
Application
Monitors the operational temperatures of the sliding contacts
Table S LED
Type
LED - Red, Green, & Yellow as both solid and flashing (0.5Hz) colors
Application
Used to indicate state of circuit breaker and CBM unit
Содержание AP.CBM.01 EIM
Страница 1: ...Instruction Bulletin 01 4IB 48070A Circuit Breaker Monitor CBM Powered by Safety ...
Страница 4: ...Powered by Safety Circuit Breaker Monitor 01 4IB 48070A This page is intentionally left blank ...
Страница 13: ...5 Safety Powered by Safety 01 4IB 48070A This page is intentionally left blank ...
Страница 29: ...Powered by Safety 21 Usage 01 4IB 48070A Figure 21 IRIM Production Assistant Screen ...