PowlVac® ARG & ARM Series 4 Vacuum Circuit Breakers
5kV & 15kV - 1200A, 2000A, & 3000A - 25kA, 36kA, 50kA, & 63kA
01.4IB.60306
2) Removing the Circuit Breaker from the
Test/Disconnected Position out of the Circuit
Breaker Compartment
Prior to removing the circuit breaker from the
circuit breaker compartment, make sure that
the control circuits are deenergized.
!
CAUTION
Prior to removing the circuit breaker from the
circuit breaker compartment, make sure the
circuit breaker is in the open position and all
springs are discharged.
!
CAUTION
a. Open the circuit breaker compartment
door.
b. Push the secondary disconnect latch
(
) to the left. This will unlock
the secondary disconnect plug,
allowing it to be removed. Remove the
secondary disconnect plug.
Removal of the secondary disconnect plug will
trip a closed breaker and discharge the main
closing spring.
!
CAUTION
c. Press the anti-rollout latch to release
the circuit breaker and pull the circuit
breaker out of the circuit breaker
compartment using the handles
(
).
Figure 13 Removing Circuit Breaker from
Compartment