6.0 System Details
13
© Baxi Heating UK Ltd 2014
6.3
Pipework
1. The sizes of flow and return pipes from the boiler should
be determined by normal methods, according to the
requirements of the system. The connections on the boiler
are 22mm.
2. A 20 °C (36°F) drop in temperature across the system is
recommended for condensing boilers. Existing radiators may
be oversized and so allow this, but where radiator sizing is
marginal it may be advisable to retain a system temperature
drop of 11°C (20°F).
NOTE: On 30 models 28mm pipe should be used to
connect to the boiler flow and return.
3. In systems using non-metallic pipework it is necessary to
use copper pipe for the boiler Flow and Return. The copper
must extend at least 1 metre from the boiler and include any
branches (Fig. 9).
6.4
Low Head Installation
1. Using a close couple arrangement the minimum head is as
shown in the diagrams (Figs. 10 & 11) subject to the
following conditions:
a) The pump being adjusted to give a 20°C drop across
the boiler.
b) The pump must be fitted on the flow.
c)
The pump must be fitted in accordance with the
pump manufacturer's instructions.
d) The open vent pipe must be taken up from a tee in a
horizontal section of the flow pipe.
An alternative Low Head Installation
(Fig. 12)
2. For heads below 400mm then a combined vent and feed
pipe may be connected. This must be a minimum of 22mm
diameter. It is recommended that an air separator is fitted
when using a combined feed and vent pipe.
6.5
Pump
1. Providing that the cold feed and open vent pipe are
positioned correctly (e.g. the system is not prone to
pumping over, air entrainment etc.) the pump may be fitted
on the primary return pipe.
Typical Low Head Installation
If Conditions Require,
This System Possible
Alternative Low Head Installation
Boiler
500mm
45°
22mm
Open Vent
1000mm
Min
150mm
Max
15mm
Cold
Feed
400mm
Min Head
Return
Pump
Flow
Boiler
500mm
45°
22mm
Open Vent
400mm
Min Head
1000mm
Min
Automatic Air
Vent
15mm
Cold
Feed
150mm
Max
Return
Pump
Flow
Return
Pump
Flow
Boiler
200mm
Min
Air
Separator
22mm
Feed & Vent
Pipe
Fig. 10
Fig. 11
Fig. 12
Boiler
Flow
Return
Copper
0.5m
Copper
1m
Copper
0.5m
Fig. 9