7.0 Site Requirements
17
© Baxi Heating UK Ltd 2009
7.7
Flue
NOTE:
Due to the nature of the boiler a plume of water
vapour will be discharged from the flue. This should be
taken into account when siting the flue terminal.
1. The following guidelines indicate the general requirements
for siting balanced flue terminals. For GB recommendations
are given in BS 5440 Pt 1. For IE recommendations are given
in the current edition of I.S. 813 “Domestic Gas
Installations”.
2. If the terminal discharges onto a pathway or passageway,
check that combustion products will not cause a nuisance
and that the terminal will not obstruct the passageway.
3. If a terminal is less than 2 metres above a balcony, above
ground or above a flat roof to which people have access,
then a suitable terminal guard must be provided.
IMPORTANT:
• Only
ONE
25mm clearance is allowed per installation.
• Under car ports we recommend the use of the plume
displacement kit.
• The terminal position must ensure the safe and
nuisance - free dispersal of combustion products.
N
I
I
G
F
M
I
A
A
F
H
J,K
D
E
H
Likely flue positions requiring
a flue terminal guard
C
R
A
I
J,K
I
L
S
B
T
U
Fig. 11
Fig. 12
300 min
Terminal
Assembly
Top View Rear Flue
Property Boundary Line
NOTE:
The distance from a fanned draught appliance terminal
installed parallel to a boundary may not be less than 300mm in
accordance with the diagram below
Terminal Position with Minimum Distance (Fig. 11)
(mm)
Aa Directly below an opening, air brick, opening
windows, etc.
300
Ba Above an opening, air brick, opening window etc.
300
Ca Horizontally to an opening, air brick, opening window etc.
300
D
Below gutters, soil pipes or drain pipes.
25
E
Below eaves.
25
F
Below balconies or car port roof.
25
G
From a vertical drain pipe or soil pipe.
25
H
From an internal or external corner.
25
I
Above ground, roof or balcony level.
300
J
From a surface or boundary line facing a terminal.
600
K
From a terminal facing a terminal (Horizontal flue).
1200
From a terminal facing a terminal (Vertical flue).
600
L
From an opening in carport (e.g. door, window)
into the dwelling.
1200
M
Vertically from a terminal on the same wall.
1500
N
Horizontally from a terminal on the same wall.
300
R
From adjacent wall to flue (vertical only).
300
S
From an adjacent opening window (vertical only).
1000
T
Adjacent to windows or openings on pitched and flat roofs
600
U
Below windows or openings on pitched roofs
2000
a In addition, the terminal should be no nearer than 150 mm to an
opening in the building fabric formed for the purpose of accommodating
a built-in element such as a window frame. See BS 5440 Pt. 1.
Opening Window
or Door
100mm
MIN.
IMPORTANT:
If fitting a Plume
Displacement Flue Kit, the air inlet
must be a minimum of 100mm from
any opening windows or doors (see
Section 9.0).
Plume
Displacement Kit
Air Inlet
Fig. 12a