12
Blocking
Sensor error
Maximum security
Ignition fault
Fan fault
Parameter error
Miscellaneous
Reset
Working to reset
Press the RESET key for 5 seconds: The status signals will flash red quickly and the boiler will start its reset proce-
dure.If the error code continues to display, search for the cause in the error table and apply the solution.
8.1.2 Lock-out (continued)
Lock-out (Status signals)
Status signals
Description
Probable causes
Checking/solution
Error Code 1
(1 x red signal)
Error Code 2
(2 x red signal)
Error Code 3
(3 x red signal)
Error Code 4
(4 x red signal)
Error Code 5
(5 x red signal)
Error Code 6
(6 x red signal)
Fan fault
Parameter
error
Miscellaneous
Ignition fault:
5 burner start-up
failures
False flame
signal
5x Flame loss
Maximum
temperature of
heat exchanger
or control unit
exceeded
Sensor fault,
temperature
fault or flow
fault
Sensor not or badly
connected
Bad connection
Non-existent or
insufficient circulation
Water circulation
direction reversed
Sensor fault
Non-existent or
insufficient circulation
Sensor not or badly
connected
Bad connection
Sensor fault
No air supply or
insufficient air supply
No flue gas flow or
insufficient flue gas
flow
Circulation
Check the wiring.
Check that the sensors are operating correctly
Check that the sensor has been correctly fitted
Vent the air in the heating system
Check the water pressure
Check the cleanliness of the heat exchanger
Check the circulation (direction, pump, valves)
Replace the sensor if necessary
Vent the air in the heating system
Check the water pressure
Check the cleanliness of the heat exchanger
Check the circulation (direction, pump, valves)
Check the wiring
Check that the sensors are operating correctly
Check that the sensor has been correctly fitted
Replace the sensor if necessary
Check air supply
Check flue gas flow
Replace seals
Check the wiring
Check breakdown to earth
Check the condition of the burner set
Check the earthing
Check that the gas valve is fully opened
Check the supply pressure
Purge the gas supply to remove air
Check the operation and setting of the gas valve unit
Check that the air inlet and flue gas discharge flues are not blocked
Replace the ionization/ignition electrode
No ignition
Ignition arc, but no
flame formation
Presence of the flame
but insufficient
ionization (<1μA)
External draught over
the boiler
Defective gas/air unit
Check for adequate draw on the chimney connection
Replace the gas/air unit
Bad connection
Safety parameters not
found
Check the wiring
Several possible
causes
The fault codes can be read with a suitable controller or the service
tool