PSN-106, PSN-64, PSB-10 • 5403590 • REV A • 12/09
For proper operation the voltage drop to the farthest connected
device must not exceed 3 volts. This can be calculated using the
following formula:
(Alarm Current of Notifi cation Appliances)
x (Wire Resistance)
< 3 volts
Notifi cation Power Supply
Install in accordance with installation manual Part Number
5403590 Rev A, NFPA 70, and NFPA 72
N G
H
Comm
Low Battery
AC Power
Gnd Fault
Battery -
Battery connection (non-power limited).
Use two (2) 12V batteries connected in series.
Common relays are
non-power limited.
120VAC 50Hz~60Hz
240VAC 50Hz~60Hz
Connect to separate
unswitched AC circuit
LOW AC
RELAY
NC COM NO
TROUBLE
RELAY
NC COM NO
B
White
Black
Ground
IN2
- + EOL
IN1
- + EOL
REF
EOL
DC PWR
- +
NAC6
- +
NAC4
- +
NAC3
- +
NAC1
- +
NAC2
- +
NAC5
- +
S1
S2
S3
S4
S5
S6
S8
S7
Trigger
- +
NAC1
NAC4
NAC5
NAC6
NAC3
NAC2
DC PWR
COMM
DC Power
- +
Status LED's
E.O.L.
ON
E.O.L.
OFF
Bulk Options
120/240 VAC
Jumper Position
GND FAULT
DETECT ENABLE
Optional
Reference
E.O.L.
Factory Installed
Interconnect.
120|240
120|240
Fuse
Primary AC
120VAC 50Hz~60Hz, 5.1AMP
Min Low AC Detect 97VAC
240VAC 50~60Hz 2.5AMP
Min Low AC Detect 190VAC
Common Relays
3A @ 125VAC (Resistive)
3A @ 30VDC (Resistive)
Battery Charging
27.3VDC @ 1A
Low Battery Detect @20.4VDC
Earth Fault to Any Terminal
0 Ohms
Notifi cation Appliance Circuits 1-6
24VDC @3A Power Limited
Regulated
Synchronization supported on NAC 1-6
DC Power Circuit
20.4VDC - 27.3VDC @3A Power Limited
Special Application RSG-DH1224
Listed Door Holder
Fuse Specifi cation
8A-250VAC Time-Lag
Note: Total current draw from NAC 1-6 and DC Power
must not exceed 10 amps.
F.C.C.
This device has been verifi ed to comply with FCC Rules Part 15,
Class A Operation is subject to the following conditions:
1. This device may not cause radio interference.
2. This device must accept any interference received including
any that may cause undesired operation.
Requirements
System must be fully tested after installation.
Intended for indoor use in dry locations only.
Separation of power limited wiring from non-power limited
wiring must be at least 1/4".
Содержание PSB-10
Страница 2: ...2 PSN 106 PSN 64 PSB 10 5403590 REV A 12 09 ...
Страница 20: ...PSN 106 16 PSN 106 PSN 64 PSB 10 5403590 REV A 12 09 This page intentionally left blank ...
Страница 36: ...PSN 64 16 PSN 106 PSN 64 PSB 10 5403590 REV A 12 09 This page intentionally left blank ...
Страница 46: ...This page intentionally left blank ...
Страница 47: ......
Страница 48: ......