background image

MFG. #5401161 -  REV d

09/12

PRINTEd IN USA

 PAGE 1 OF 8

MODEL PS40 (VdS)

SUPERVISORY PRESSURE SWITCH

Models: 

PS40-1 VdS 

 

 

 

 

 

PS40-2 VdS

Installation 

The Potter PS40 Series Supervisory Pressure Actuated Switches are designed 

primarily to detect an increase and/or decrease from normal system pressure 

in  automatic  fire  sprinkler  systems.    Typical  applications  are:  Dry  pipe 

systems, pre-action air/nitrogen supervision, pressure tanks, air supplies, 

and water supplies.   The PS40 switch is factory set for 2,8 BAR (40 PSI) 

normal system pressure.  The switch marked with the word LOW is set to 

operate at a pressure decrease of ,7 BAR (10 PSI) at 2,1 BAR (30 PSI).  The 

switch marked with the word HIGH is set to operate at a pressure increase 

of ,7 BAR (10 PSI) at 3,5 BAR (50 PSI).  See section heading 

Adjustments 

and Testing

 if other than factory set point is required.

1.  Connect the PS40 to the system side of any shutoff or check valve. 

 

2.  Apply Teflon tape to the threaded male connection on the device.          

     (do not use pipe dope) 

 

 

 

 

 

3.  device should be mounted in the upright position.   

    

       

     (Threaded connection down)  

 

 

 

 

4.  Tighten the device using a wrench on the flats on the device. 

Wiring Instructions 

1.  Remove the tamper resistant screw with the special key provided. 

 

2.  Carefully place a screwdriver on the edge of the knockout and sharply                   

     apply a force sufficient to dislodge the knockout plug.  See Fig. 9 

 

3.  Run wires through an approved conduit connector and affix   

 

     the connector to the device.  A NEMA-4 rated conduit fitting is required

     for outdoor use. 

4.  Connect the wires to the appropriate terminal connections for the 

     service intended. See Figures 2,4,5,6, and 8

UL,  cUL,  and  CSFM  Listed,  FM  and  LPC  Approved,  NYMEA 

Accepted, CE Marked, VdS 
Dimensions: 

(9,6cm) 3.78" W x (8,1cm) 3.20" D x (10,7cm) 4.22" H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                            

 

 

 

 

 

 

 

 

 

 

Enclosure:    

Cover- Die-cast with textured red powdercoat finish, single                    

                       cover screw and rain lip.     

 

 

 

 

      Base- die-cast                                                   

Pressure Connection: 

Nylon 1/2" NPT male

Potter Electric Signal Company

 • St. Louis, MO • Customer Service: 866-572-3005 • Tech Support: 866-956-0988 •

 Canada 888-882-1833

 

 www.pottersignal.com

Cover  incorporates  tamper  resistant  fastener  that  requires  a 

special key for removal.  One key is supplied with each device.  

For optional cover tamper switch kit, order Stock No. 0090200.  

See bulletin #5401200 PSCTSK.

Switch Contacts: 

 SPdT (Form C)  

                               10.1 Amps at 125/250VAC, 2.0 Amps at 30VdC

                               One SPdT in PS40-1, Two SPdT in PS40-2

Environmental Specifications:  

 

 

 

 

 

 

NEMA 4/IP66 Rated Enclosure - indoor or outdoor when used   

 

with NEMA 4 conduit fittings.

 

Temperature range: -40°C to 60°C (-40°F - 140°F)   

Pressure Range:  

0,7 - 4,1 BAR (10-60 PSI)

Differential:    

Typical 0,07 at 0,7 BAR (1 lb. at 10 PSI) 

 

 

        0,28 at 4,1 BAR (4 lbs. at 60 PSI)

Maximum System Pressure:  

17,2 BAR (250 PSI)

Service Use

 

Automatic Sprinkler 

NFPA-13

 

One or two family dwelling 

NFPA-13d

 

Residential Occupancy up to four stories 

NFPA-13R

 

National Fire Alarm Code 

NFPA-72

Factory Adjustment: 

PS40-1 operates on decrease at 2,1 BAR (30 PSI)

PS40-2 operates in increase at 3,5 BAR (50 PSI) and 

on decrease at 2,1 BAR (30 PSI)

Conduit Entrance:

Two knockouts provided for 1/2" conduit. Individual 

switch compartments and ground screw suitable for 

dissimilar voltages.

Tamper:

Adjustment And Testing

The operation of the supervisory pressure switch should be tested upon 

completion of installation and periodically thereafter in accordance with 

the applicable NFPA codes and standards and/or the authority having 

jurisdiction (manufacturer recommends quarterly or more frequently). 

 

 

 

 

 

 

 

Note:

  Testing the PS40 may activate other system connected devices.   

The use of a Potter BVL (see product bulletin 8900067 for details) is 

recommended to facilitate setting and testing of the PS40 pressure switch. 

When a BVL (bleeder valve) is used, the pressure to the switch can be 

isolated and bled from the exhaust port on the BVL without effecting the 

supervisory pressure of the entire system.  See Fig. 3 

                

 

 

 

 

 

 

The operation point of the PS40 Pressure Switch can be adjusted to any 

point between 0,7 - 4,11 BAR (10 and 60 PSI) by turning the adjustment 

knob(s) clockwise to raise the actuation point and counter clockwise to 

lower the actuation point.  In the case of the PS40-2, both switches operate 

independent of each other.  Each switch may be independently adjusted to 

actuate at any point acrosss the switch adjustment range.  Initial adjustment 

can be made with a visual reference from the top of the adjustment knob 

across to the printed scale on the switch bracket.  Final adjustments should 

be verified with a pressure gauge. 

 

Содержание PS40 SERIES

Страница 1: ... supplied with each device For optional cover tamper switch kit order Stock No 0090200 See bulletin 5401200 PSCTSK Switch Contacts SPDT Form C 10 1 Amps at 125 250VAC 2 0 Amps at 30VDC One SPDT in PS40 1 Two SPDT in PS40 2 Environmental Specifications NEMA 4 IP66 Rated Enclosure indoor or outdoor when used with NEMA 4 conduit fittings Temperature range 40 C to 60 C 40 F 140 F Pressure Range 0 7 4 ...

Страница 2: ...RE DROP WITH NORMAL SYSTEM PRESSURE APPLIED HIGH TERMINAL 1 WILL CLOSE ON PRESSURE INCREASE NOTE To prevent leakage apply teflon tape sealant to male threads only ADJUSTMENT KNOB 2 87 72 97 4 22 107 19 2 48 62 87 3 78 95 89 3 20 81 28 1 60 40 64 Fig 4 An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections The wire must be severed...

Страница 3: ...RESSURE SWITCH Switch Operation Low Pressure Signal Connection EOLR TO FIRE ALARM PANEL EOLR TO FIRE ALARM PANEL High Pressure Signal Connection Fig 5 Fig 7 With normal system pressure Terminal C Common 1 Closed when installed under normal system pressure 2 Open when installed under normal system pressure Closes on pressure drop Use for low air signal Terminal 1 Open when installed under normal sy...

Страница 4: ...ce before servicing Serious injury or death could result Read all instructions carefully and understand them before starting installation Save instructions for future use Failure to read and understand instructions could result in improper operation of device resulting in serious injury or death Risk of explosion Not for use is hazardous locations Serious injury or death could result Do not tighte...

Страница 5: ...gewindeverbindungen verwenden 3 Die Vorrichtung sollte in aufrechter Position montiert werden Gewindeanschluss nach unten 4 Ziehen Sie die Vorrichtung an indem Sie nur die flachen Seiten eines Schraubenschlüssels am Gerät ansetzen 1 Entfernen Sie die manipulationsresistente Schraube mit dem beiliegenden Spezialschlüssel 2 Führen Sie am Rand derAusbrechöffnung vorsichtig einen Schraubendreher ein u...

Страница 6: ...MDRUCK HOCH ANSCHLUSS 1 SCHLIESST BEI DRUCKANSTIEG Abb 4 ERDUNGS SCHRAUBEN 1 2 NPT HINWEIS Bringen Sie an den Außengewinden Teflonband an um Leckagen zu vermeiden EINSTELLKNOPF 2 87 72 97 4 22 107 19 2 48 62 87 3 78 95 89 3 20 81 28 1 60 40 64 Ein abisolierter Abschnitt eines einzelnen Leiters sollte nicht um dieAnschlussklemme geschlungen werden um ihn anstelle von zwei separaten Verbindungen zu ...

Страница 7: ...rucksignal Anschluss Für Hochdrucksignal Abb 5 Abb 7 bei normalem Systemdruck Anschluss C Gemeinsame Leitung 1 Geschlossen bei Installation unter normalem Systemdruck 2 Geöffnet bei Installation unter normalem Systemdruck Schließt bei Druckabfall Verwendung für Signal bei niedrigem Luftdruck Anschluss 1 Geöffnet bei Installation unter normalem Systemdruck Schließt bei Druckanstieg Verwendung für S...

Страница 8: ...rleitungsöffnungen eine für jede Schalterkammer um die Verwendung unterschiedlicher Spannungen für die einzelnen Schalter zu erleichtern Die Abdeckung des Druckschalters besteht aus Zinkdruckguss mit Regenschutz und ist mit einer manipulationsresistenten Schraube zu befestigen Der Druckschalter kann sowohl im Innenbereich als auch imAußenbereich mit NEMA 4 IP66 Klassifizierung verwendet werden Der...

Отзывы: