background image

MFG. #5400932 - REV D-1

12/10

PRINTED IN USA

 PAGE 3 OF 3

PS100-2

PRESSURE TYPE FLOW SWITCH

Fig. 8

DWG#928-5

Fig. 9

Removing Knockouts

Changing Pressure 

(with normal system pressure)

C

C

1

2

         SWITCH ONE

SWITCH TWO

C

C

1

2

DWG# 932-3

Engineer/Architect Specifications Pressure Type 

Waterflow Switch 

Pressure type waterflow switches; shall be a Model PS100-2 as 

manufactured by Potter Electric Signal Company, St. Louis, MO., 

and shall be installed on the fire sprinkler system as shown and or 

specified herein.

Switches shall be provided with a ½" NPT male pressure connection 

to be connected to the excess pressure supply line on the system 

side of any shut-off  or check valve.  A Model BVL bleeder valve as 

supplied by Potter Electric Signal Company  of St. Louis, MO., or 

equivalent shall be connected in line with the PS100-2 to facilitate 

testing of the PS100-2.

Pressure type waterflow switches shall have a maximum service 

pressure rating of 300 PSI (20,68 BAR) and shall be factory adjusted 

•Installation must be performed by qualified personnel and in

  accordance with all national and local codes and ordinances.

•Shock hazard. Disconnect power source before servicing.  

  Serious injury or death could result.

•Read all instructions carefully and understand them before  

  starting installation. Save instructions for future use. Failure  

  to read and understand instructions could result in improper   

  operation of device resulting in serious injury or death.

•Risk of explosion.  Not for use is hazardous locations.  

  Serious injury or death could result.

•Do not tighten by grasping the switch enclosure. Use wrenching  

  flats on the bushing only.  Failure to install properly could  

  damage the switch and cause improper operation resulting in   

  damage to equipment and property.

•To seal threads, apply Teflon tape to male threads only. Using  joint    

  compounds or cement can obstruct the pressure port  inlet and result  

  in improper device operation and damage to equipment.

•Do not over tighten the device, standard piping practices apply.

to operate on a pressure decrease of 10 PSI (14,5 BAR).

Pressure switch shall have two Form C contacts, switch contact rating 

at 10.1 Amps at 125/250 VAC. 2.0 Amps at 30 VDC. 

 

Pressure type waterflow switches shall have two conduit entrances, 

one for each individual switch compartment to facilitate the use of 

dissimilar voltages for each individual switch.

The cover of the pressure type waterflow switch shall be zinc die-cast 

with rain lip and shall attach with one tamper resistant screw.  The 

pressure type waterflow switch shall be suitable for indoor or outdoor 

service with a NEMA-4/IP66 rating.                                                   

The pressure type waterflow switch shall be UL, ULC, and CSFM 

listed, FM and LPC approved and NYMEA accepted.

#1: Closed under normal system pressure.

#2: Open under normal system pressure, closes on pressure      

       drop. Use as waterflow detector.

Отзывы: