background image

MFG. #5400932 - REV D-1

12/10

PRINTED IN USA

 PAGE 1 OF 3

PS100-2

PRESSURE TYPE FLOW SWITCH

Installation

The Potter PS100 Pressure Actuated Switches are designed primarily to detect 

a decrease from normal system pressure in automatic fire sprinkler systems.  

A typical application is for an alarm initiating device that is used on a wet 

system with excess pressure.  The PS100-2 has two SPDT switches factory 

set to operate on a pressure drop at 90 PSI (6,2 BAR).  See section heading 

Adjustments and Testing

 if other than factory set point is required.

1.  Connect the PS100 to the system side of any shutoff or check valve. 

 

2.  Apply Teflon tape to the threaded male connection on the device.          

     (Do not use pipe dope) 

 

 

 

 

 

3.  Device should be mounted in the upright position.   

    

       

     (Threaded connection down)  

 

 

 

 

4.  Tighten the device using a wrench on the flats on the device.

Wiring Instructions 

1.  Remove the tamper resistant screw with the special key provided. 

 

2.  Carefully place a screwdriver on the edge of the knockout and sharply                   

   apply a force sufficient to dislodge the knockout plug.  See Fig. 9

3.  Run wires through an approved conduit connector and affix the 

   connector to the device.  A NEMA-4 rated conduit fitting 

   is required for outdoor use.

4.  Connect the wires to the appropriate terminal connections for the 

   service intended.  See Figures 2,4,5,7, and 8.  See Fig. 6 for two 

   switch one conduit wiring.

UL,  cUL,  and  CSFM  Listed,  FM  and  LPC  Approved,  NYMEA 

Accepted, CE Marked
Dimensions: 

3.78" (9.6cm)W x 3.20" (8.1cm)D x 4.22" (10.7cm)H

Conduit Entrance: 

Two knockouts provided for 1/2" conduit. 

 

 

Individual switch compartments and ground screw    

 

 

suitable for dissimilar voltages.  

 

 

Enclosure:    

Cover- Die-cast with textured red powdercoat finish, single                    

                       cover screw and rain lip.     

 

 

 

 

      Base- Die-cast                                                   

Pressure Connection: 

Nylon 1/2" NPT male

Factory Adjustment:  

Operates on decrease at 90 PSI (6,2 BAR)

Pressure Range:  

25-175 PSI (1,7 - 12,1 BAR)

Differential:  

Typical 2 lbs. at 25 PSI (,14 at 1,7 BAR)               

             

      8 lbs at 175 PSI (,55 at 12,1 BAR)

Maximum System Pressure: 

300 PSI (20,68 BAR)

Switch Contacts: 

 Two SPDT (Form C)  

                               10.1 Amps at 125/250VAC, 2.0 Amps at 30VDC

Environmental Specifications:  

 

NEMA 4/IP66 Rated Enclosure - indoor or outdoor when 

used with NEMA-4 conduit fittings.

 

Temperature range: -40°F to 140°F (-40°C to 60°C)

Tamper:  

Cover incorporates tamper resistant fastener that requires 

 

a  special  key  for  removal.  One  key  is  supplied  with  each  device.   

 

For optional cover tamper switch kit, order Stock No. 0090200.  

 

See bulletin #5401200 PSCTSK.

Service Use:

 

Automatic Sprinkler 

NFPA-13

 

One or two family dwelling 

NFPA-13D

 

Residential Occupancy up to four stories 

NFPA-13R

 

National Fire Alarm Code 

NFPA-72

Potter Electric Signal Company

 •

 St. Louis, MO 

 Customer Service: 866-572-3005 

• Tech Support: 866-956-0988 •

 Canada 888-882-1833

 

 www.pottersignal.com

Adjustment And Testing

The operation of the waterflow pressure switch should be tested upon 

completion of installation and periodically thereafter in accordance with 

the applicable NFPA codes and standards and/or the authority having 

jurisdiction (manufacturer recommends quarterly or more frequently).

Note: 

 Testing the PS100 may activate other system connected devices.   

The use of a Potter BVL (see product bulletin 8900067 for details) is 

recommended to facilitate setting and testing of the PS100 pressure 

switch. When a BVL (bleeder valve) is used, the pressure to the switch 

can be isolated and bled from the exhaust port on the BVL without 

effecting the supervisory pressure of the entire system.  See Fig. 3
The operation point of the PS100 Pressure Switch can be adjusted to any 

point between 25 and 175 PSI (1,7 - 12,1 BAR) by turning the adjustment 

knob(s) clockwise to raise the actuation point and counter clockwise to 

lower the actuation point.  Both switches operate independent of each 

other.  Each switch may be independently adjusted to actuate at any point 

acrosss the switch adjustment range.  Initial adjustment can be made 

with a visual reference from the top of the adjustment knob across to the 

printed scale on the switch bracket.  Final adjustments should be verified 

with a pressure gauge. 

 

Ordering Information 

 

 

 

 

Model 

 

Description 

 

 

Stock No.

PS100-2 

Pressure switch with two SPDT contacts   1341005   

 

Hex Key                                                      5250062

 

Cover Tamper Switch Kit                           0090200

BVL 

Bleeder valve                                              1000018

Отзывы: