Figure 11B: Main Fire Alarm Module Terminal Connections (cont’d)
When wiring devices, please keep in mind the following:
All terminals are shown from the back of the main
fi
re alarm board assembly (pointing towards the rear of the enclosure).
•
All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
•
Initiating circuits are fully supervised and rated for 26 VDC, 3 ma standby, 1.5 Vp-p ripple, 50 mA max. alarm. They may
•
be con
fi
gured as required. Maximum loop resistance is 100 ohms, 50 ohms per side.
Initiating circuits are compatibility ID “A”.
•
SUPERVISORY OR
W ATERFLOW
SWITCH (NO)
HEAT DETEC TOR
LEGEND:
See Appendix A
for compatible devices.
SMOKE DETEC TOR
3.9K 1/2W ELR LISTED S5434
MODEL MP-300 MANUFACTURED
BY MIRCOM
PULL STATION
S
-
RS-485
1,
2,
OR 3 REMOTE ANNUNCIATORS
SEE APPLICABLE OPERATION & INS
T
ALL ATION
MAN UAL.
(N OT USED WITH R TI)
CLASS B /
STYLE 4 WIRING
24VDC POWER +
(POWER LIMITED) -
-
+
4-WIRE
SUPPLY
INI1+
INI1-
INI2+
INI2-
INI3+
INI3-
INI4+
INI4-
STYLE D
INI2
STYLE D
INI1
CLASS B /
STYLE B
WIRING
CLASS A /
STYLE D
WIRING
SUPERVISED INITIATING CIRCUIT #4
(SHOWN AS SUPV ZON E,
POWER LIMITED)
SUPERVISED INITIATING CIRCUIT #3
(SHOWN AS ALARM
ZON E,
POWER LIMITED)
SUPERVISED INITIATING CIRCUIT #1
(POWER LIMITED)
RESETTABLE 4-WIRE
SMOKE DETEC TOR POWER
LIMITE D,
POWER SUPPLY
.
28 VDC,
100 mA MAX.,
1.5VP-P RIPPLE.
COM+
RTI REMOTE TROUBLE INDIC AT OR (NOT SUPERVISED)
(N OT USED WITH RAM-208'S)
TRB
RTI
INTER
FACE
TRL
+
EXAMPLES OF BOTH CLASS A AND B WIRING ARE SHOWN,
BUT
ONLY ONE CLASS OF WIRING MAY BE USED IN ANY INSTALLATION.
CLASS B /
STYLE B
WIRING
COM-
(SEE FIG.11)
BLU
RS-485 INTERFACE
(POWER LIMITED)
AUX.
POWER POSITIVE
BLK
RED & WHT
RT I
UNFILTERED SPECIAL APPLIC ATION