PFC-3005T Installation and Operation Manual
11
Underwriter’s Labs Inc. (ULI) United States 2-Wire Smoke Detector
Control Panel Compatibility
Notes:
• Reset time, hold for five seconds minimum.
• Whether mixing different models of compatible smoke detectors, or using the same
model on the same circuit, total standby current of all detectors must not exceed 3
mA.
• The below-listed smoke detectors are compatible with initiating circuits having
Compatibility Identifier "A".
Smoke
Detector
Make Model /
Base
Compatibility
Identifier
Head / Base
Rated
Standby
Current
Smoke Detector
Make Model /
Base
Compatibility
Identifier Head /
Base
Rated Standby
Current
System Sensor
Sentrol - ESL
1100
A - N/A
0.12 mA
429C
S10A - N/A
0.10 mA
1151/
B110LP
A - A
0.12 mA
429CT
S10A - N/A
0.10 mA
1151/
B116LP
A - A
0.12 mA
429CST
S11A - N/A
0.10 mA
1400
A - N/A
0.10 mA
429CRT
S11A - N/A
0.10 mA
1451/B401
A - A
0.12 mA
711U/701E,
701U, 702E,
702U
S10A - S00
0.10 mA
1451/
B401B
A - A
0.12 mA
712U / 701E,
701U, 702E,
702U
S10A - S00
0.10 mA
1451/
B406B
A - A
0.12 mA
713-5U / 701E,
701U, 702E,
702U
S10A - S00
0.10 mA
1451DH/
DH400
A - A
0.12 mA
713-6U / 701E,
701U, 702E,
702U
S10A - S00
0.10 mA
2100
A - N/A
0.12 mA
721U / 702E,
702U
S10A - S00
0.10 mA
2100T
A - N/A
0.12 mA
721UT / 702E,
702U
S10A - S00
0.10 mA
2151/
B110LP
A - A
0.12 mA
722U / 702E,
702U
S10A - S00
0.10 mA
2151/
B116LP
A - A
0.12 mA
731U / 702E,
702U, 702RE,
702RU
S11A - S00
0.10 mA