RELEASING CIRCUIT

One Class B circuit
Circuit is power limited
Circuit is rated 24VDC at 1 Amp continuous, 3 Amps intermittent
Reverses polarity to release extinguishing agent
Operates at the end of the pre-discharge timer period (or upon actuation of a manual alarm if this mode is selected for the
manual alarm circuit.)
Minimum battery voltage that will maintain 85 - 100% of solenoid voltage = 22.5 Volts
Maximum allowable line resistance =  2 ÷ CURRENT (IN RELEASE MODE)
Maximum short circuit loop current is 8 mA (in standby condition)
Normal standby loop current is 3 mA
End-Of-Line resistor is 5.1k ohms

ABORT CIRCUIT

One Class B switch circuit
Circuit is power limited
Maximum loop resistance is 100 ohms
Maximum short circuit loop current is 8 mA
Normal standby loop current is 3 mA.
End-Of-Line resistor is 5.1k ohms
Two switch selectable modes of operation:

Mode 1 - The release of the extinguishing agent is delayed as long as the abort switch is activated.  Deactivation of the

abort switch will result in the release of the extinguishing agent within 10 seconds if the 60 second delay period
has elapsed.

Mode 2 - (IRI Mode)  If the abort switch is actuated prior to the actuation of a second alarm, the pre-discharge timer will

not start.  If the abort switch is restored after the second alarm, subsequent actuation of the abort switch will not
interrupt the operation of the pre-discharge timer.  Actuation of the abort switch after a second alarm will not
interrupt operation of the pre-discharge timer.

PRE-DISCHARGE TIMER

Switch selectable from 0 to 60 seconds in 10 second increments, with 4 switch selectable modes of operation for the smoke/heat
detector circuits (the predischarge circuit, also switch selectable, to be 0 or 30 seconds upon activation of the manual circuit):

Mode 1 Single Zone

 - Actuation of one or more detectors will create an alarm condition and start the pre-discharge timer (this

mode is usually used with heat detectors).

Mode 2 Cross Zone 

- Actuation of one or more detectors in any one zone will create an alarm condition.  Actuation of one or

more detectors in both zones, in addition to creating an alarm condition will start the pre-discharge timer (this mode is usually
used with smoke detectors).

Mode 3  Sequential

 - Actuation of one detector in any one zone will create an alarm condition.  Actuation of a second detector

in the same zone will start the pre-discharge timer (this mode is usually used with smoke detectors).

Mode 4 Sequential or Cross Zone

 - Actuation of one detector in any zone will create an alarm condition.  Actuation of two

detectors in the same zone, or one detector in each zone will start the pre-discharge timer (this mode is usually used with smoke
detectors).

Manual Circuit Activation

 - Activation of one or more devices on the Manual Device Circuit will create an alarm condition.

The output of this circuit is switch selectable to start a 30 second pre-discharge timer or to immediately activate the releasing
circuit.  Activation of this circuit overrides abort.

DISCHARGE TIMER

firealarmresources.com

Содержание PFC 2000RC

Страница 1: ...CT TO REVISION MANUAL 5403521 REVN 3 03 2081 Craig Road P O Box 28480 St Louis MO 63146 4161 800 325 3936 314 878 4321 FAX 314 878 7264 www pottersignal com INSTALLATION OPERATION AND INSTRUCTION MANU...

Страница 2: ...ion or repair by unauthorized per sons or if for any other reason POTTER determines that said product is not operating prop erly as a result of causes other than defective manufacture labeling or pack...

Страница 3: ...PLIANCE CIRCUITS 8 RELEASING CIRCUIT 9 ABORT CIRCUIT 9 PRE DISCHARGE TIMER 9 DISCHARGE TIMER 9 POWER REQUIREMENTS 10 AUXILIARY POWER OUTPUT 10 AUDIBLE INDICATOR 10 ELECTRONIC OUTPUTS 10 AUXILIARY CONT...

Страница 4: ...ION INSTRUCTIONS 16 PROCEDURE FOR THE REMOVAL OF THE MAIN BOARD MODULE 16 LOCATION 16 MOUNTING THE BEZEL 17 INSTALLATION OF BEZEL FOR SEMI FLUSH INSTALLATIONS DRAWING 17 WIRING HOOKUP 17 TEST PROCEDUR...

Страница 5: ...all alarm trouble and supervisory conditions in an English format 10 One man test feature 11 Compatible with 2 and 4 wire detectors 12 Power limited circuits 13 Single alarm trouble silence switch 14...

Страница 6: ...m condition Discharged Red LED comes on when releasing circuit is activated Supervisory Yellow LED comes on for supervisory condition System Trouble Yellow LED comes on for any trouble condition Possi...

Страница 7: ...circuits RESET SWITCH Momentary switch resets all alarm circuits if the condition has been corrected Removes power from the alarm initiating device circuit and also from the auxiliary power circuit if...

Страница 8: ...equired for alarm is 5 mA Normal standby loop current is 3 mA End of line resistor is 5 1k ohms Minimum time to reset is 3 seconds SUPERVISORY INITIATING DEVICE CIRCUIT One Class B circuit Circuit is...

Страница 9: ...the abort switch after a second alarm will not interrupt operation of the pre discharge timer PRE DISCHARGE TIMER Switch selectable from 0 to 60 seconds in 10 second increments with 4 switch selectab...

Страница 10: ...IC OUTPUTS 24VDC 25mA with current limiting to 45mA for each of the following Alarm per zone 3 System Trouble Releasing Circuit activated System Alarm Supervisory Output for optional 4 pole relay see...

Страница 11: ...lay 2 Operation of the red alarm LED 3 Operation of the auxiliary alarm contacts 4 Positive 24 VDC will appear on the associated zone electronic output terminal 5 Operation of one or both of the indic...

Страница 12: ...he problem must be located and corrected SUPERVISORY CONDITION An increase in current to approximately 4 5 mA or greater in the supervisory circuit will result in the following 1 The words SUPV and SU...

Страница 13: ...er located on the power supply board will be illuminated AUXILIARY POWER FAILURE Failure of the auxiliary power supply will result in the following 1 The words TROUBLE and AUX POWER will be displayed...

Страница 14: ...on of a indicating appliance circuit that is the result of a current in excess of 1 5 Amps when the panel is in the alarm condition requires manual operation of the Reset switch SELECTING PANEL OPERAT...

Страница 15: ...ISCHARGE TIMER ACTIVATION MODE There are 4 modes of starting the pre discharge timer from zones 1 and or 2 Select the desired mode by setting switches 9 and 10 as shown in the following Mode Operation...

Страница 16: ...arm Code Central Station Proprietary and Local all local codes and the authority having jurisdiction Review the circuit parameters listed in the Specifications section of this manual before installing...

Страница 17: ...st procedure section TEST PROCEDURES CAUTION The system should be inspected and tested in compliance with NFPA 72 National Fire Alarm Code or the authority having jurisdiction 1 Notify the fire depart...

Страница 18: ...e test has been concluded OPERATINGINSTRUCTIONS Fill in the name address and telephone number of the servicing agency on the instruction sheet provided and post in a prominent place There are two Oper...

Страница 19: ...tor Required AH x 001 x____ x 001 __ 85 TABLE 1 CURRENT REQUIREMENTS Module Device Standby mA Alarm mA PFC2000RC 85 240 Includes one zone short circuit current TABLE 2 SECONDARY POWER SUPPLY REQUIREME...

Страница 20: ...AND OR CLASS 2 SOURCE ONLY 8 AUXILIARY POWER 24V MAX FOR LIMITATIONS SEE SECTION BATTERY SIZE REQUIREMENTS COMBINED LOAD ON THESE TERMINALS NOT TO EXCEED 500 MA MAX SEE SECTION ON COMPATIBILITY DATA...

Страница 21: ...evice intended specifically for this purpose or by the use of one or more listed alarm pressure switches installed to monitor the pressure present in the suppression system the normally open contacts...

Страница 22: ...y Activation Mode Selected 6 Dia Base 4 Dia Base Impedance Contact 1 or 2 single or cross zone HSB 221N YBA M221 390 ohms no HSC 221R 390 ohms yes 3 or 4 sequential or cross sequential HSB 221 YBA M21...

Страница 23: ...23 PFC 2000RC 5403521 REV N 3 03 CONNECTION DRAWING POWER SUPPLY MODULE TYPICAL 4 WIRE DETECTOR CONNECTION DRAWING CLASS B CKT SHOWN firealarmresources com...

Страница 24: ...24 PFC 2000RC 5403521 REV N 3 03 CONNECTION DRAWING FOR CENTRAL STATION PROPRIETARY OPERATION PFC EFT C INTERCONNECTION DRAWING PFC ATTE B INTERCONNECTION DRAWING firealarmresources com...

Страница 25: ...25 PFC 2000RC 5403521 REV N 3 03 PFC 2000RC INNER PANEL DRAWING firealarmresources com...

Страница 26: ...HB 71 NS6 221 NS4 221 SLR 24H HD 3 HSB 221N HB 54 HSB 221 HB 54 HSC 221R HB 71 NS6 221 NS4 221 SIJ 24 HD 3 HSB 221N HB 54 HSB 221 HB 54 HSC 221R HB 71 NS6 221 NS4 221 FENWAL MAX NO OF DETECTORS PER ZO...

Страница 27: ...M 2 C 1 1 1 C O N V L N U 4 N B 8 1 2 3 7 C D V 4 2 r e l k n i r p S l a r t n e C A l e d o M 6 c n I o C r e l k n i r p S c i t a m o t u A e l b a i l e R A l e d o M X B d n a B s l e d o M 2 1...

Страница 28: ...way from power input wiring battery leads and any other non power limited conductors NOTE All field installed wiring connected to this panel must maintain a spacing of 1 4 inch between all power limit...

Отзывы: