
E. Addressing
Detector address can be configured using the
table below for DIP switch position settings
.
POS DIP Switch on POS DIP Switch on POS DIP Switch on
1
1
43
1,2,4,6
85
1,3,5,7
2
2
44
3,4,6
86
2,4,5,7
3
1,2
45
1,3,4,6
87
1,2,3,5,7
4
3
46
2,3,4,6
88
4,5,8
5
1,3
47
1,2,3,4,6
89
1,4,5,7
6
2,3
48
5,6
90
2,4,5,7
7
1,2,3
49
1,5,6
91
1,2,4,5,7
8
4
50
2,5,6
92
3,4,5,7
9
1,4
51
1,2,5,6
93
1,3,4,5,7
10
2,4
52
3,5,6
94
2,3,4,5,7
11
1,2,4
53
1,3,5,6
95
1,2,3,4,5,7
12
3,4
54
2,3,5,6
96
6,7
13
1,3,4
55
1,2,3,5,6
97
1,6,7
14
2,3,4
56
4,5,6
98
2,6,7
15
1,2,3,4
57
1,4,5,6
99
1,2,6,7
16
5
58
2,4,5,6
100
3,6,7
17
1,5
59
1,2,4,5,6
101
1,3,6,7
18
2,5
60
3,4,5,6
102
2,3,6,7
19
1,2,5
61
1,3,4,5,6
103
1,2,3,6,7
20
3,5
62
2,3,5,5,6
104
4,6,7
21
1,3,5
63
1,2,3,4,5,6
105
1,4,6,7
22
2,3,5
64
7
106
2,4,6,7
23
1,2,3,5
65
1,7
107
1,2,4,6,7
24
4,5
66
2,7
108
3,4,6,7
25
1,4,5
67
1,2,7
109
1,3,4,6,7
26
2,4,5
68
3,7
110
2,3,4,6,7
27
1,2,4,5
69
1,3,7
111
1,2,3,4,6,7
28
3,4,5
70
2,3,7
112
5,6,7
29
1,3,4,5
71
1,2,3,7
113
1,5,6,7
30
2,3,4,5
72
4,7
114
2,5,6,7
31
1,2,3,4,5
73
1,2,4,7
115
1,2,5,6,7
32
6
74
3,4,7
116
3,5,6,7
33
1,6
75
1,3,4,7
117
1,3,5,6,7
34
2,6
76
2,3,4,7
118
2,3,5,6,7
35
1,2,6
77
1,3,4,7
119
1,2,3,5,6,7
36
3,6
78
2,3,4,7
120
4,5,6,7
37
1,3,6
79
1,2,3,4,7
121
1,4,5,6,7
38
2,3,6
80
5,7
122
2,4,5,6,7
39
1,2,3,6
81
1,5,7
123
1,2,4,5,6,7
40
4,6
82
2,5,7
124
3,4,5,6,7
41
1,4,6
83
1,2,5,7
125
1,3,4,5,6,7
42
2,4,6
84
3,5,7
126
2,3,4,5,6,7
127
1,2,3,4,5,6,7
Testing must meet the requirements of the Authority Having
Jurisdiction (AHJ). It is recommended to follow guidelines as
described in NFPA 72.
It is important to test the product after installation and
periodically to ensure it functions probably.
Heat Test
Use hair dryer or heat gun to direct the heat toward the side
of the detector. Keep at a distance of 6 in or 15 cm to avoid
overheating.
Units failing the heat test should be serviced.
Magnet Test
The magnet test provides a quick test to verify the connections
and the detector electronically. This test should not replace the
aerosol test, which is required as part of regular testing and
maintenance per NFPA 72.
1. Hold the test magnet in the magnet test area as shown
below.
2. The LED flashes rapidly to indicate the detector is in
alarm.
3. Remove magnet.
4. Alarm on the fire alarm panel should be reset.
5. Unit failed the magnet test should be tested again
with heat gun or hair dryer to confirm the failure.
F. Testing
NOTIFY APPROPRIATE AUTHORITY BEFORE
TESTING THE DETECTOR. PLACE FIRE PANEL IN
WALK TEST
MODE BEFORE CONDUCTING THE FOLLOWING TEST. REFER
TO THE PANEL INSTALLATION MANUAL FOR DETAIL.
CAUTION
Magnet Location
POTTER warrants that the equipment herein shall conform
to said descriptions as to all affirmation of fact and shall be
free from defects of manufacture, labeling, and packaging for
a period of five (5) years from the invoice date to the original
purchaser, provided that representative samples are returned
to POTTER for inspection. The product warranty period is
stated on the exterior of the product package. Upon a de-
termination by POTTER that a product is not as warranted,
POTTER shall, at its exclusive option, replace or repair said
defective product or parts thereof at its own expense, except
that Purchaser shall pay all shipping, insurance, and similar
charges incurred in connection with the replacement of the
defective product or parts thereof. This Warranty is void in
the case of abuse, misuse, abnormal usage, faulty installation,
or repair by unauthorized persons, or if for any other reason
POTTER determines that said product is not operating prop-
erly as a result of causes other than defective manufacture,
labeling, or packaging.
G. Warranty
Manual Number:
54035210X_A
Manual Issue Date:
07/01/2022