The PAD300-HD is an intelligent addressable thermal detector 

with a programmable fixed temperature and a 15oF/min rate 

of rise alarm.
Each detector includes one (1) LED to indicate the device 

status. The LED flashes momentarily in normal conditions and 

flashes at a fast rate when activated. The LED can be turned off 

using the programming software.
The PAD300-HD is listed on maximum 70 ft spacing with 

alarm set point from 135oF to 185oF on smooth ceiling. 

Refer to NFPA 72 for specific information regarding detector 

spacing, placement and special applications.
The PAD300-HD communicates on a proprietary protocol to 

the addressable fire alarm control panel. It must be connected 

to either the IPA series, AFC series, or ARC fire alarm 

control panel for proper operation. For detector sensitivity 

settings and supervision, please refer to the panel installation 

instructions.
Refer to the company website for the latest revision of this 

manual.

A.  Introduction

1609 Park 370 Pl, Hazelwood, MO 63042

www.pottersignal.com

PAD300-HD

Operating Voltage

24 VDC

Standby Current (*)

300 μA

Alarm Indicator Current

1.4 mA

Alarm Temp Rating

Installation Temp Range

135oF to 174oF

32oF to 115oF

Alarm Temp Rating

Installation Temp Range

175oF to 185oF

32oF to 150oF

Operating Humidity Range

0% - 93% (Non-condensing)

Dimension

Φ 3.93 in

Weight 

2.4 oz

Height

1.5 in

*Standby current is the current the device consumes when the device 

is in a non-activated condition and where no communication current 

is transmitted to the fire alarm control panel. 

Sensitivity-Spacing Allocation:

The sensitivity of PAD300-HD heat detector is expressed in 

terms of spacing limitations. Spacing limitations refer to the 

maximum distance permitted between heat detectors mounted 

on smooth ceilings.

See below table for the UL521 spacing limitations.

Spacing Allocation

Fixed Temperature 135ºF to 

185oF

70 ft

w/ Rate of Rise 15oF/min

70 ft

NOTE:

THE DEFAULT FIXED ALARM TEMPERATURE IS 135oF 

WITH THE RATE-OF-RISE FUNCTION DISABLED. BOTH SET-

TINGS CAN BE CHANGED IN THE POTTER PROGRAMMING 

SOFTWARE. FOR FURTHER INFORMATION, REFER TO THE 

CONTROL PANEL INSTALLATION INSTRUCTIONS.

B.  Specifications

Installation must meet the requirements of the Authority 

Having Jurisdiction (AHJ). It is recommended to follow 

guidelines as described in NFPA 72. 

1.  Before connecting a device to the SLC loop, take the 

following precautions to prevent potential damage to the 

SLC or device.

•  Use only the PAD300 series bases PAD300-4DB, 

PAD300-6DB, PAD300-SB, PAD300-LFSB (supplied 

separately).

•  Confirm the field wiring on device is correctly 

installed on the base. Refer to the base manual.

•  Enable the locking feature if needed. Refer to section 

D for details of the locking feature.

2.  Set the desired address using the DIP switch located 

on back of the sensor. See section E for addressing 

instructions.

3.  Plug detector into base and turn clockwise to secure in 

place. 

C.  Installation

The device includes a tamperproof feature that locks the detec-

tor and does not allow removal without the use of a tool. 

D.  Locking Feature

Break off tab (gray area in 

image). The 

locking feature

 

is enabled.

Insert a small 

screwdriver into slot 

to remove detector.

                     

DETECTORS ARE NOT TO BE USED WITH 

DETECTOR GUARDS UNLESS THE COMBINATION HAS BEEN 

EVALUATED AND FOUND SUITABLE FOR THAT PURPOSE.