INSTALLATION MANUAL:  PAD100-TRTI TWO RELAY TWO INPUT MODULE

Document 5406303-A  02/16

Potter Electric Signal Company, LLC           •           St. Louis, MO             •           Phone: (800) 325-3936               •            www.pottersignal.com

 

PAGE 2 OF 3

When the PAD100-TRTI is used to monitor two individual Class B circuits a single device address is assigned; each input and 

relay is then identified as a sub-point of the module address. For example, if the address number is assigned as "8", the "RLY1" 

relay will be identified as "8.1", the "RLY2" relay will be identified as "8.2", the "B1" input will be "8.3", and the "B2" input will be 

"8.4."
Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the SLC or device.

• 

Power to the SLC is removed.

• 

Field wiring on module is correctly installed.

• 

Field wiring has no open or short circuits.

3.  Technical Specifications

Operating Voltage

24.0V

Max SLC Standby Current

240 μ A

Max SLC Alarm Current

240 μ A

Relay Contacts

2A @30VDC, 0.5A @125VAC

Max Wiring Resistance of IDC

100 Ω

Max Wiring Capacitance of IDC

1μF

Max IDC Voltage

2.05 VDC

Max IDC Current

120 μ A

EOL Resistor

5.1K Ω

Operating Temperature Range

32

̊ 

to 120

̊ 

F (0

̊ 

to 49

̊ 

C)

Operating Humidity Range

0 to 93% (non-condensing)

Max no. of Module Per Loop

127 units

Dimensions

4.17" L x 4.17" W x 1.14" D

Mounting Options

UL Listed 2-1/2" deep 2-gang box or  

1-1/2" deep 4" square box

Shipping Weight

0.6 lbs

4.  Wiring Diagrams

The following wiring diagrams illustrate how to wire a PAD100-TRTI module as a Class A and Class B circuit. Additionally, an 

installation diagram shows how to install the module using a compatible electrical box. 

Figure 3. 

Example of Installing a PAD100-TRTI Using a Compatible Electrical Box