MKT. #8830008- REV A-3

04/13

PRINTED IN USA

PAGE 1 OF 2

DCM-4

Dual ContaCt MoDule

Potter Electric Signal Company, LLC • St. Louis, MO • Cust Service: 866-240-1870 • Tech Support: 866-956-1211 • Canada: 888-882-1833

 

• www.pottersignal.com

All terminals are power limited and should be wired in accordance 

with the requirements of NFPA 70 (NEC) and NFPA 72 (National Fire 

Alarm Code). Failure to follow the wiring diagrams in the following 

pages will cause the system to not operate as intended. For further 

information, refer to the control panel installation instructions.

For more information, refer to a compatible fire panel installation. 

Operation and Programming Manual. 

Description

The Dual Contact Module, DCM-4 is used to supervise multiple 

contact points with unique addresses from a single device. In addition, 

the DCM-4 may be configured as a single contact utilizing Class A 

wiring methods. 
The DCM-4 is fully supervised if wired in accordance with the wiring 

diagrams below. Normally closed contact monitoring is not UL listed.
The DCM-4 employs one red LED to indicate the status. In normal 

condition, the LED flashes. When the contact is activated, the LED 

will turn on constantly. In case of open circuit, the LED will turn off. 

If the conditions of two contacts are different from each other with 

two contacts supervising, the LED shall activate with higher priority 

condition. The highest priority of contact condition is activated 

condition of contact, the middle priority is open circuit, and the lowest 

priority is normal condition.
Since the system allows a maximum of 13 LEDs to activate constantly, 

if system already has 13 LEDs active on devices, DCM-4 will not turn 

on the LED and keep flashing even if the contacts of DCM-4 are in the 

active state.

Setting the Address

Each addressable module, smoke sensor, heat detector and 

combination sensor/detector must have the address set before 

connecting the device to the SLC loop. The address is set using the 

hand held device programmer or the addressing feature on the control 

panel.
Before connecting a device to the SLC loop, take the following 

precautions to prevent potential damage to SLC or device. Verify the 

following:

1. 

Power to the device is removed

2. 

Field wiring is correctly installed.

3. 

Field wiring has no open or short circuits.

Document discrepancies and notify appropriate personnel.

A dedicated address number is configured per the DCM-4 module 

prior to connecting the module to SLC loop. When DCM-4 is used for 

two contacts supervising, two addresses are assigned. When the first 

address number is assigned by address setting unit, the second address 

number shall be assigned automatically with adding one (1) to first 

address number. For example, if the first address number is assigned as 

“2”, the second address number shall be assigned as “3” automatically.

Product includes a 5 year warranty

S2930 7165-0328:0196

Features

• 

Single contact module with dual inputs

• 

Two (2) Class B and one (1) Class A input module

• 

SLC Class A (Style 6, 7) & Class B (Style 4)

• 

IDC wiring may be Class B (Style B) or Class A (Style D)

• 

All connections are power limited

• 

Wiring for all connections is supervised 

• 

Terminals accept 14 to 22 AWG wire

• 

Mounts in 4” square box with terminals accessible

• 

Temperature range of 32°F–120°F

• 

Maximum loop current draw of 325 μA

Note: This addressable module does not support 2-wire smoke 

detectors