AK355 System Installation and User's Guide
Positron Access Solutions
11
180-0037-002 R01
1.3.2
Rear View
The rear views of the AK355 systems are similar less the DS3 connections on
the AK355E model.
1.3.2.1 Frame Ground Connections
The Ground Lug located on the right hand side of the back panel (see Figure 4)
can accommodate up to 6 AWG wire. Use a wire gauge for grounding at least as
heavy as the power wiring. Attach the grounding wire to the AK355 Ground Lug
to a nearby grounding screw on the equipment rack or facility ground. Test the
ground connection with an ohm meter; there should be less than 2 ohms
between the AK355 Ground Lug and facility ground.
Note that the ground connection is required for proper system operations.
Figure 4 AK355 Rear View
Содержание AK355
Страница 1: ...AK355 System Installation and User s Guide...
Страница 25: ...AK355 System Installation and User s Guide Positron Access Solutions 25 180 0037 002 R01...
Страница 26: ...AK355 System Installation and User s Guide Positron Access Solutions 26 180 0037 002 R01...
Страница 32: ...AK355 System Installation and User s Guide Positron Access Solutions 32 180 0037 002 R01...
Страница 51: ...AK355 System Installation and User s Guide Positron Access Solutions 51 180 0037 002 R01...
Страница 53: ...AK355 System Installation and User s Guide Positron Access Solutions 53 180 0037 002 R01...
Страница 95: ...AK355 System Installation and User s Guide Positron Access Solutions 95 180 0037 002 R01...
Страница 96: ...AK355 System Installation and User s Guide Positron Access Solutions 96 180 0037 002 R01...
Страница 109: ...AK355 System Installation and User s Guide Positron Access Solutions 109 180 0037 002 R01...
Страница 120: ...AK355 System Installation and User s Guide Positron Access Solutions 120 180 0037 002 R01...
Страница 163: ...AK355 System Installation and User s Guide Positron Access Solutions 163 180 0037 002 R01 Appendices...