Porter 6256-3 Скачать руководство пользователя страница 2

2.

PIPING REQUIREMENTS

2.1. 

Sedation Outlet Connections (N

2

O/O

2

)

This

 portion of the 6256-3 outlet station has 

the option of unscrewing the gas block,
(N

2

O/O

2

) (Fig. 2) from the support plate 

(three screws), inverting the block (Fig. 3) so 
the pipes may extend downward (Fig. 4). 

2.2. 

IMPORTANT:

When remounting the 

blocks to the support plate use the 

lower

 set 

of holes on the plate (Fig. 4) to insure the
faceplate will line up.  (Note: This is only 
when pipes are pointing down.) 

2.3.  Pipes can then be joined to their appropriate 

3/8” OD tube for Nitrous Oxide, and ½” OD 
tube for Oxygen.  (See section below.) 

2.4. 

Central Suction Powered Systems:

Determine the direction in which the piping 
is needed.   

2.5.  If the vacuum tube (1/2” OD) is required in 

the upward position, be aware that moisture 
could drain back into the tubing.  It is 
recommended that a trap be used. 

2.6.  If the vacuum tube (1/2” OD) is required in 

the downward position, unscrew the vacuum 
block from the support pole (two screws), 
invert the block (Fig. 5) and screw the 
vacuum block back onto the support plate.  

2.7. 

IMPORTANT:

When remounting the block 

to the support plate use the

upper

 set of

holes on the plate.  (Note: This is only when 
pipe is pointing down.) 

3.

DRYWALL OR WALL BOARD CUT-
OUT AND STATION FIXTURING
DETAILS

3.1.  Closing up walls requires a 2 ¾” H. x 6 3/8” 

L. cut-out opening.  See template diagram 
for actual cut-out outline. 

3.2.  Bracket “B” butts up to underside of drywall.  

Pan Head tapping screws with washers, 
pinch drywall in place for fastening right end 
of unit securely. 

4.

INSTALL THE GAS SUPPLY LINES:

Note: The station is designed and intended to be
used with gas supply lines installed using NFPA
99 guidelines, including a 150 PSI piping integrity
test.  Medical grade dry Nitrogen should be used
as a “forming gas” while soldering.  To prevent
oxidation inside supply lines:
(a)  Use type K or L, pre-cleaned, degreased,

capped copper tubing ONLY. 

(b)  Use 3/8” O.D. for Nitrous Oxide; use ½” O.D. 

for Oxygen.  DO NOT CHANGE TUBING 
DIAMETERS!! 

(c)  All copper to copper joints are to be made 

using a brazing allows conforming to AWS 
Classification BcuP-5 (see AWS Std. A5.8).  
Flux shall not be used. 

(d)  After connecting all gas lines, check the 

system for leaks with dry Nitrogen per NFPA 
99. 

5.

Check for Crossed Lines.

  (Refer to NFPA

Gas and Vacuum Systems Code for Type II
Systems)  (See 

cross+protection Warning

in

this brochure.)

3

AFTER DRY WALL IS INSTALLED 

6.

Remove cover cap.  Check to make sure leading
edge of box is flush with dry wall.  If U shaped
bracket is incorrectly aligned, loosen bracket
mounting nuts with a 3/8” open end wrench,
adjust to fit, re-tighten nuts.

7.

Alignment & Adjustment for Front Plate
Installation – The Oxygen and Nitrous Oxide
Valve Bodies are factory adjusted to allow for the
back of the Front Plate to press against the metal
surfaces of all three valve bodies.  If adjustment
is needed, follow these steps:
7.1.  Rotate the Oxygen and Nitrous Oxide valve

bodies so they both uniformly contact the 
back of the Front Plate. Oxygen has right 
hand threads and Nitrous Oxide has left 
hand threads.

7.2.  Adjust the right hand thread vacuum valve 

body to align with the metal surfaces of the 
other valve bodies.  

4

8.

Install Front Plate with the six 4-40 flat head
screws.

9.

Apply diameter indexed N

2

O/O

2

gas label in

place over diameter indexed check valve
connector bushings.  Pull off center strip backing,
and press label in place.  Remove top and
bottom backing strips, and finish securing label.

10. Connect an 8060 series duplex connector and

hoses into the completely assembled Triple
Outlet Station.  Attach the other end of the hoses
to a flowmeter and turn the flow control knobs to
the off position and the on/off switch to the off
position.

11.

Leak test the entire system for working
pressure leaks.

Pressurize the sedation gas

supply lines with 50 PSI.  Observe any pressure
decay after 12 hours.  This 50 PSI test with the
flowmeter tubing connections in place tests the
seal of the duplex connector extended into the o-
rings of the outlet station primary check valves.
(5 PSI drop allowed.)

12. Attach the appropriate vacuum lines from the

HVE attachment to the station vacuum line.

CONNECTIONS TO FLOWMETER – 
OPERATING INSTRUCTIONS 

Flowmeter Gas Supply Tubing and Vacuum Tubing is
connected to the Triple Outlet Station via two quick 
connect couplers.  The Porter 8060 series duplex 
connector simultaneously connects the Oxygen and 
Nitrous oxide tubing, and prevents the Nitrous Oxide 
from being connected unless the Oxygen is 
connected.  The Porter 5602 vacuum quick connect 
with hose barb separately inserts into the vacuum 
check valve of the station.  

QUICK CONNECTING 

You may quick connect to the station when the 

system pressure is at its normal 50 PSI; the primary 
check valves seal this pressure.  Both couplers have 
locating latches.  Simply insert the couplers into the 
appropriate check valve and confirm the latch is in 
place behind the catch feature of the valve.  A gentle 
tug on the coupler will confirm a stable latch position.
Internally, within the primary check valve, an o-ring
seals against a poppet.  The same o-ring seals 
against the quick connect extensions upon insertion.   
Slide the latch out of position to remove the 
connector and the internal poppet will automatically 
move back into its sealing position. 

RESUSCITATOR 

Remove the duplex connector so a resuscitator quick 
connects may be inserted into the oxygen station 
position. 

MAINTENANCE AND SERVICE 

Use Scavenging 

Monitor for N2O in the operator to insure that  
controls are effective in achieving low levels of ppm 
(parts per million) exposure. Contact your Porter 
dealer for details on monitors and testing. 

Inspect and maintain

 the analgesia delivery 

system to prevent N2O leaks in all hoses,
connections and fittings.  Repair all leaks 
immediately.

Fig. 2

Fig. 3

Fig. 4

DRYWALL CUT-OUT

(ACTUAL SIZE)

2

3

4

"

6

3

8

"

BRACKET “A”

TEMPLATE DIAGRAM

(2) 

3

16

"

dia. holes

STUD

See note #7

Fig. 5

BRACKET

“A”

BRACKET

“B”

BRACKET

“B”

Cut-Out

Right Edge

6

3

8

"

2

3

4

"

For Stock

No. 6256-3

1"

6

3

4

"

7

1

2

"

4

3

4

"

2

1

8

"

Fits into
Standard
2 x 3/2 x 4
Construction
Wall

PULL

3

4

2

Отзывы: