September 2020
17
PoolPak PCP Series
–
Outdoor OMM
Control System
The dehumidifier control system is composed of sensors, spread throughout the dehumidifier,
Main Control
Board
,
Operator Panel
and other electric components, located in the
Main Electric Panel.
Temperature Sensors
(Pic. D.2):
a)
Temperature
sensors
(thermistors) are used to monitor
various temperatures (air, water, compressor, etc.);
b)
Combo
sensor is used to monitor air temperature and
humidity.
Compressor operation is monitored with
pressure sensors
(Pic. D.3):
c)
Pressure Transducers
(as main operational control and safety) and
d)
Pressure Switches
(fast-reacting backup safety).
Sensors and safeties approximate location is shown on Pic. D.4-L and D.4-B (see below).
•
RA Combo
Sensor
(21) measures temperature and humidity of the pool room air (Return Air) entering the
dehumidifier. It is located at the return air ductwork connection to thedehumidifier.
•
OA Temperature Sensor
(22) measures outdoor air temperature; it’s located at the OA filter rack.
o
As an option, the combo sensor (instead of regular thermistor) can be installed at the OA intake to
measure both the temperature and humidity of the outdoor air.
•
ET (EvapT) Temperature Sensor
(23) measures the temperature of air leaving evaporator coil. I
t’s located
directly downstream of the evaporator.
•
SA temperature sensor
(24) measures the temperature of the air leaving the dehumidifier (supplied to the
premise). It must be located
downstream of the space heater
:
o
In some cases, where the space heater is external to dehumidifier, the sensor will be provided with
the dehumidifier to be field-mounted into the supply air ductwork downstream of the space heater.
•
If the dehumidifier is equipped with the pool heating option, the
Pool Water Temperature sensors
(
Pool In
(25) and
Pool Out
(26)) measure the entering and leaving pool water temperature. The sensors are located
directly at the respective connections of the coaxial pool water heat exchanger.
o
As an option, the pool water heat exchanger piping/manifold may have water flow switch also.
•
The c
ompressor’s discharge line (high pressure side) is equipped with Temp
erature and Pressure sensors set -
Discharge Temperature Sensor, High Pressure Transducer
and
High Pressure Switch
(27) - to protect the
compressor and control its operation. A similar function is performed by
Suction Temperature Sensor, Low
Pressure Transducer
and
Low Pressure Switch
(28) located at compressor’s suction line (low pressure side).
•
If dehumidifier is equipped with
Heat Recovery
option, it could also have
Exhaust Air
(EA)
T
emperature
Sensor
(29), installed downstream of exhaust-side located heat recovery glycol coil.
•
Main Electric Panel,
apart from devices listed above (control board, OP, etc.) also contains
Voltage Monitor;
some optional control sensors and devices such as an air pressure differential sensor, current sensor(s). It may
also be located in main electrical panel or in the dehumidifier in general.
b
a
c
d
Pic.D.3
Pic. D.2