PoolPak PCP Series 

 Outdoor OMM

 

Control System 

The dehumidifier control system is composed of sensors, spread throughout the dehumidifier, 

Main Control 

Board

Operator Panel

 and other electric components, located in the 

Main Electric Panel.

  

Temperature Sensors 

(Pic. D.2):  

a)

 

Temperature

 sensors

 

(thermistors) are used to monitor 

various temperatures (air, water, compressor, etc.); 

b)

 

Combo

 sensor is used to monitor air temperature and 

humidity. 

 

 

 

 

 

 

 

Compressor operation is monitored with 

pressure sensors

 (Pic. D.3):  

c)

 

Pressure Transducers

 (as main operational control and safety) and 

 

d)

 

Pressure Switches

 (fast-reacting backup safety).

 

 

 

Sensors and safeties approximate location is shown on Pic. D.4-L and D.4-B (see below).  

 

RA Combo

 

Sensor

 (21) measures temperature and humidity of the pool room air (Return Air) entering the 

dehumidifier. It is located at the return air ductwork connection to thedehumidifier. 

 

OA Temperature Sensor

 

(22) measures outdoor air temperature; it’s located at the OA filter rack.

 

o

 

As an option, the combo sensor (instead of regular thermistor) can be installed at the OA intake to 
measure both the temperature and humidity of the outdoor air.  

 

ET (EvapT) Temperature Sensor

 (23) measures the temperature of air leaving evaporator coil. I

t’s located 

directly downstream of the evaporator. 

 

SA temperature sensor

 (24) measures the temperature of the air leaving the dehumidifier (supplied to the 

premise). It must be located 

downstream of the space heater

o

 

In some cases, where the space heater is external to dehumidifier, the sensor will be provided with 
the dehumidifier to be field-mounted into the supply air ductwork downstream of the space heater. 

 

If the dehumidifier is equipped with the pool heating option, the 

Pool Water Temperature sensors

 (

Pool In

 

(25) and 

Pool Out

 (26)) measure the entering and leaving pool water temperature. The sensors are located 

directly at the respective connections of the coaxial pool water heat exchanger.  

o

 

As an option, the pool water heat exchanger piping/manifold may have water flow switch also. 

 

The c

ompressor’s discharge line (high pressure side) is equipped with Temp

erature and Pressure sensors set - 

Discharge Temperature Sensor, High Pressure Transducer 

and

 High Pressure Switch

 (27) - to protect the 

compressor and control its operation. A similar function is performed by 

Suction Temperature Sensor, Low 

Pressure Transducer 

and

 Low Pressure Switch

 

(28) located at compressor’s suction line (low pressure side).

 

 

If dehumidifier is equipped with 

Heat Recovery

 option, it could also have 

Exhaust Air

 

(EA)

 T

emperature 

Sensor 

(29), installed downstream of exhaust-side located heat recovery glycol coil. 

 

Main Electric Panel,

 apart from devices listed above (control board, OP, etc.) also contains

 Voltage Monitor;

 

some optional control sensors and devices such as an air pressure differential sensor, current sensor(s). It may 
also be located in main electrical panel or in the dehumidifier in general.

  

Pic.D.3

 

Pic. D.2

 

Содержание PCP 3000

Страница 1: ...PoolPak com OPERATION AND MAINTENANCE MANUAL DEHUMIDIFIERS PCP SERIES Outdoor...

Страница 2: ...entilation 22 Space Heating 22 Air Conditioning Dehumidification and Pool Heating 22 Compressor s 22 Sequence of Operation 8 to 20 tons 24 Ventilation 24 Purge Additional Exhaust Option 24 Heat Recove...

Страница 3: ...w safety procedures can result in serious injury or death Beware of moving parts and hot surfaces Make sure to stop all moving parts fans blowers etc before accessing the equipment s internal space Be...

Страница 4: ...com Attention Installation and Service Contractors WARNING Any work installation start up service maintenance repair etc on any mechanical equipment dehumidifier outdoor condenser fluid cooler etc mu...

Страница 5: ...talled externally fitted in the supply air ductwork or internally Refer to your dehumidifier s submittal documentation Gas fired heater can be installed externally within supply ductwork Alternatively...

Страница 6: ...e brought to the gas heater directly Attention Equipment Clearances and Dimensions CAUTION For equipment proper operation maintenance and service respective clearances should be maintained Generally 3...

Страница 7: ...idifier View and Options BX Cab Standard PCP1400 to PCP6000 dehumidifier general views as well as some options are shown on Pic C 1 Pic C 1 shows only one example of dehumidifier arrangement refer to...

Страница 8: ...minations end sides o Optional Purge Outdoor Air POA ductwork connection termination top sides Optional Pool Water Heating Optional Space Heating hot water coil electric or gas heater Optional Heat Re...

Страница 9: ...ide Space heating Hot Water connection bottom side o Some connection location options for both pool and space heating pipe lines are limited to indoor installation only refer to submittal documentatio...

Страница 10: ...mpressor refrigeration circuit Single and Two Compressor Arrangement Dehumidifier Model Dehumidifier typical arrangement total capacity and number of compressors are reflected in its model for specifi...

Страница 11: ...s dehumidifier may have different condenser provided with it refer to the dehumidifier s submittal documentation for more details Two compressor dehumidifier would normally have paired up two outdoor...

Страница 12: ...tandard dehumidifier and cooler combination depending on number of factors dehumidifier may have different cooler provided with it refer to the dehumidifier s submittal documentation for more details...

Страница 13: ...e dehumidifier to show External systems connections location direction pool space heating cooling circuits condensate Air filter locations quantity and size Additional Info warning caution stickers et...

Страница 14: ...ows all most available options some of which may not be present on your dehumidifier Dehumidifier Main Components SLX Main Blower 1 is in the main blower compartment next to the Main Electric Panel 2...

Страница 15: ...eater electric and control panel 62 and provisions for combustion air intake 63 and flue exhaust 64 o Pipe chase opening 65 in Compressor Compartment and Gas Heater Package floors allow for external s...

Страница 16: ...urge exhaust fan and Purge Outdoor Air openings Refrigeration coils Evaporator 7 and Reheat internal condenser 8 are located directly downstream of the Main Filter Rack 9 o Evaporator Bypass Damper 10...

Страница 17: ...PoolPak PCP Series Outdoor OMM 16 September 2020 11b 2 1 3 5 4 7 8 9 11a 10 13 14 15 18 17 16 Pic D 1 B 19 74 72 75 71 74 6 71 76 76 76 76 77...

Страница 18: ...midifier supplied to the premise It must be located downstream of the space heater o In some cases where the space heater is external to dehumidifier the sensor will be provided with the dehumidifier...

Страница 19: ...PoolPak PCP Series Outdoor OMM 18 September 2020 27 21 23 24 22 28 25 26 Pic D 4 L...

Страница 20: ...September 2020 19 PoolPak PCP Series Outdoor OMM Pic D 4 B 29 26 25 27 28 21 22 23 24...

Страница 21: ...ot gas Liquid etc In some cases fluid cooler piping connection s may be located within pump package box 37 if fluid cooler is provided with one Piping connection location may vary refer to particular...

Страница 22: ...to the fluid cooler directly standard or provided separately Pump 38 establishes glycol mixture circulation through the fluid cooler and dehumidifier Expansion tank 39 compensates for temperature base...

Страница 23: ...r Dehumidification operation Note Externally installed Exhaust Fan s and Outdoor Air damper s could be also controlled by the dehumidifier control system This applies to both Minimum and Purge Additio...

Страница 24: ...uid Cooler Operation below Once demand for the compressor s operation is removed respective call is satisfied the pump down solenoid valve closes once the compressor suction pressure reaches the pre s...

Страница 25: ...OA damper if dehumidifier is equipped with such option opens to introduce fresh outdoor air into the premise OA damper could be equipped with ON OFF simple fully open fully closed or modulating contr...

Страница 26: ...ll for Air Conditioning Mode Respectively when premise air humidity goes over exceeds its set point the dehumidifier control system issues a call for Dehumidification Mode In some instances these call...

Страница 27: ...r operation related safeties and timers are confirmed by the control system the pump down solenoid valve opens and once pressure stabilizes the compressor starts Based on the premise air temperature t...

Страница 28: ...ans type and wiring diagram if when needed If the fluid cooler is equipped with the built in pump package to establish cooling fluid flow between dehumidifier and the fluid cooler or to serve as addit...

Страница 29: ...ced Access to advanced settings and features Help Context sensitive help presenting information related to the viewed page Most common basic maintenance tasks performed using Touch Display OP Adjust S...

Страница 30: ...asing voltage etc is outside of pre set limits Check Voltage Monitor info status incoming power voltage Compressor HP1 X LP1 X SupHeat1 DisTemp1 Various compressor related alarms relevant to Compresso...

Страница 31: ...ate RJ 45 jack plastic black is mounted on the control board directly for TouchDisplay connection Make sure to use the proper jack metal surface one located on the sub board for Web Monitor connection...

Страница 32: ...erforming any equipment maintenance work make sure that all moving parts are stopped and it is safe to perform required task Maintenance Key Points Here are some basic key maintenance considerations p...

Страница 33: ...gged or dirty Verify that all set points are correctly programmed as specified by the facility operator Semi Annually Inspect and clean the drain pan s Tighten electrical connections if required Check...

Страница 34: ...oils Warning Hazardous chemicals Cleaning agents can be highly acidic or alkaline Handle all chemicals carefully and use appropriate personal protective equipment PPE Refer to the cleaning agent manuf...

Страница 35: ...place for entire system fluid cooler piping dehumidifier etc Have each local high point of the system equipped with means to bleed the air air bleeding valve etc Have each local low point of the syste...

Страница 36: ...ts are covered by PoolPak manufacturer warranty All parts and labor requirements will either be handled by DASV technicians directly or managed and approved in advance by DASV through DASV authorized...

Страница 37: ...mechanical rooms that house chemicals i e chlorine bromine water treatment chemicals Products on which payment is in default 2 Parts that wear out due to normal usage such as air filters fuses and se...

Страница 38: ...months from factory ship date whichever comes first and cover parts replacement only for parts that fail as a result of manufacturing defect The failed parts must be returned to the factory with tran...

Отзывы: