When all settings are complete, hold down “SET” button 3 seconds or leave
controller with no operation 15 seconds, system will save setting changes and
return to normal working mode.
Applicable Power Supply
100-125V 60Hz
Maximum Rated Current
10A
Maximum Total Output
1100W
Temperature Setpoint Range
-
40~212℉
Temperature Resolution
0.1℉
(-4.0~158
℉
)
Menu
Code
Function
Setting
Range
Default
Setting
DT
Day Time Start Hour
0-24H
6H
NT
Night Time Start Hour
0-24H
18H
dS
Daytime Temperature Setpoint -40.0~212
℉
77.0℉
nS
Nighttime Temperature Setpoint -40.0~212
℉
77.0℉
dF
Differential value
1.0-
30.0℉
2.0℉
AL
Low Alarm Point
-
40~212℉
-
40℉
AH
High Alarm Point
-
40~212℉
212℉
Pt
Compressor Delay
0~10min
0min
CA
Temperature Calibration
-20.0~20.0
℉
0
℉
CF
℃/℉ Display
℃/℉
℉