Polyamp PU1000 Скачать руководство пользователя страница 5

      

PU1000/PU600 INSTALLATION MANUAL

 

  

 

 

                                            

 

10229-15.doc

Polyamp AB, Sweden 

www.polyamp.com 

Page 

5 (10) 

 

4. Connect the input cables. Bundle input cables 
together at the terminals separated from the output 
cables. Make the same arrangement on the output 
side. This is to make sure one cable will not bridge 
the insulation barrier in case of coming lose. 
 
5. Start the converter with your external input 

disconnection device. 

 

Beware of hazardous voltages! 

 

The output voltage can be ad10% to 
-5%  of nominal output voltage with the 
potentiometer marked V.ADJ on the front 
panel. Clockwise turn increases the output 
voltage. The potentiometer has 15 turns. If 
you are using current sharing, the procedure 
of adjusting the output voltage is described 
in 

3.3 

Voltage adjustment with current

 

sharing

 

on page 6.  

5. 

 

Replace plastic cover.

 

6. 

 

When the converter is disconnected, switch-off 
the input voltage with the disconnecting unit. 
Disconnect the input cables first, then output 
and last the protective case connection. 

 

3  Parallel connection 

If a redundant power supply system is requested, 
two or more converters can be connected in 
parallel. To achieve redundancy the number of 
converters must be dimensioned to carry the whole 
load even if one converter is faulty. Connect your 
load to the + output after the series diode, see 

Figure 1

Another reason for connecting two or more 
converters in parallel is to get more power. Use the 
output with series diode, see 

Figure 1

You should 

not use external sense

 when the unit 

are in parallel on the output. 

3.1  Series diode on the output 

The series diode protects the converter output from 
external voltage sources. A series diode is 
necessary if the output is connected in parallel with 
another power supply or if you require redundant 
operation. If a converter breaks down with an 
internal short-circuit on the output and other 
converters are connected in parallel on the output, 
the broken unit will short-circuit the others if the 

series diode is not used. This might cause excessive 
heat or even fire in the faulty unit. 

If the series diode is used, the alarm relay will 
switch to ”ALARM” on the faulty unit if one 
converter breaks down in a redundant power supply 
system. Otherwise there will be no alarm indication 
from a faulty converter unless all units are in 
current limit and the output voltage drops 10% 
below nominal output voltage. 

When the series diode is used the total output 
power of the converter must be 

derated. 

See data

 

sheet.

 

 

On 24Vd.c. output by 10%.  

 

On 48Vd.c. output by 5%. 

 
Do not forget to fuse the inputs separately to 
achieve redundancy. 

3.2  Current sharing 

All models include the automatic current sharing 
feature, which we recommend to use in parallel 
configuration. A maximum of 10 (10) units can be 
connected in parallel. 

If more than 10 units should be connected in 
 parallel, contact Polyamp. 
  
Connect a cable (0.25-1.0mm

2

) with a maximum 

length of 3.0m between the ”CURRENT SHARE” 
connectors of all units.  
 
The converter with the highest output voltage will 
then automatically become ”current master”. This 
converter will then run with a few percent higher 
output current than the others. If the master 
converter for some reason breaks down, another  
converter automatically becomes ”current master”.  

To achieve good power sharing, the voltage drop 
between the minus poles must be kept as low as 
possible, see 

Figure 1

. The plus poles can either be 

connected as in 

Figure 1

 or have separate cables to 

the load.  

At light load (if the total load is less than 5% of the 
total rated power) the yellow ”C. MASTER” LED 
might flicker between the units. As the load 
changes different units ”C. MASTER” LED might 
be lit. All this is normal. 

Содержание PU1000

Страница 1: ...PU1000 PU600 INSTALLATION MANUAL 10229 15 doc Polyamp AB Sweden www polyamp com Page 1 10 PU1000 PU600 Installation manual...

Страница 2: ...information may have been updated since then Polyamp AB reserves the right to make changes in this manual without notice The exclamation point within an equilateral triangle is intended to alert the u...

Страница 3: ...5 2 OVER TEMPERATURE 7 6 SENSE 7 6 1 EXTERNAL SENSE 7 6 2 INTERNAL SENSE 8 7 INHIBIT 8 8 OUTPUT OVER VOLTAGE PROTECTION 8 9 INRUSH CURRENT LIMIT 8 10 ISOLATION VOLTAGE TEST 8 10 1 DC ISOLATION TEST OU...

Страница 4: ...l disconnection device which is able to disconnect both polarities shall be incorporated with the input power supply cord The disconnection device must be properly labelled and easy accessible 2 Insta...

Страница 5: ...ly or if you require redundant operation If a converter breaks down with an internal short circuit on the output and other converters are connected in parallel on the output the broken unit will short...

Страница 6: ...ntil the C MASTER LED is lit or almost lit 4 Multiple loads at the output If you are using several loads we recommend fusing them separately with fast acting fuses on the positive output branch Some c...

Страница 7: ...r and connector pin marked NORMAL Figure 3 Alarm contact The relay is isolated 2500Va c from input output and case The relay can switch maximum 30V 5A a c and d c values 5 1 Over and under voltage ala...

Страница 8: ...hibit 8 Output over voltage protection All models are equipped with an internal output over voltage protection circuit OVP It consists of an additional voltage regulator operating in parallel with the...

Страница 9: ...solation test input to output and input to case above but test with 4000Vd c instead of 2000Vd c The leakage current should not exceed 5 A AC isolation test 1 Disconnect all cables from the converter...

Страница 10: ...ay be under sized causing too high voltage drop in the supply cables 2 Your supply does not have enough current capacity so the input voltage to the converter drops below specified limit 11 4 The conv...

Отзывы: