background image

      

PU1000/PU600 INSTALLATION MANUAL 

 

 

10229-15.doc

Polyamp AB, Sweden 

www.polyamp.com 

Page 

1 (10) 

 
 
 
 
 

PU1000/PU600 

Installation manual 

 

 
 

 

 
 

Содержание PU1000

Страница 1: ...PU1000 PU600 INSTALLATION MANUAL 10229 15 doc Polyamp AB Sweden www polyamp com Page 1 10 PU1000 PU600 Installation manual...

Страница 2: ...information may have been updated since then Polyamp AB reserves the right to make changes in this manual without notice The exclamation point within an equilateral triangle is intended to alert the u...

Страница 3: ...5 2 OVER TEMPERATURE 7 6 SENSE 7 6 1 EXTERNAL SENSE 7 6 2 INTERNAL SENSE 8 7 INHIBIT 8 8 OUTPUT OVER VOLTAGE PROTECTION 8 9 INRUSH CURRENT LIMIT 8 10 ISOLATION VOLTAGE TEST 8 10 1 DC ISOLATION TEST OU...

Страница 4: ...l disconnection device which is able to disconnect both polarities shall be incorporated with the input power supply cord The disconnection device must be properly labelled and easy accessible 2 Insta...

Страница 5: ...ly or if you require redundant operation If a converter breaks down with an internal short circuit on the output and other converters are connected in parallel on the output the broken unit will short...

Страница 6: ...ntil the C MASTER LED is lit or almost lit 4 Multiple loads at the output If you are using several loads we recommend fusing them separately with fast acting fuses on the positive output branch Some c...

Страница 7: ...r and connector pin marked NORMAL Figure 3 Alarm contact The relay is isolated 2500Va c from input output and case The relay can switch maximum 30V 5A a c and d c values 5 1 Over and under voltage ala...

Страница 8: ...hibit 8 Output over voltage protection All models are equipped with an internal output over voltage protection circuit OVP It consists of an additional voltage regulator operating in parallel with the...

Страница 9: ...solation test input to output and input to case above but test with 4000Vd c instead of 2000Vd c The leakage current should not exceed 5 A AC isolation test 1 Disconnect all cables from the converter...

Страница 10: ...ay be under sized causing too high voltage drop in the supply cables 2 Your supply does not have enough current capacity so the input voltage to the converter drops below specified limit 11 4 The conv...

Отзывы: