ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - User Manual

 14

7) Troubleshooting Guide

PROBLEM

SUGGESTED ACTION

Dampers have no  

response when turned on 

or off

•  Check if the ‘Safety is Activated’ error is displayed. High limit (Heating)  

  or Low limit (Cooling) may have reached. Check the air-conditioner to 

  see if it is operating normally. ZoneTouch V2 system will resume to  

  operational after the supply air temperature is within safety range.
•   *Check if Supply air sensor is plugged in the mainboard and High Limit  

  & Low Limit is enabled. If the sensor is not plugged in, plug the  

  sensor and the system will be operational after a minute. If the sensor  

  is not required, disable High limit and Low limit from touchpad and  

  system will return to operational in a minute.
•   *Check if LEDs on the main module light up for relevant zones when  

  the zone dampers are being turned On/Off. If Green/Red LEDs are not  

  activated for the respective zone, the main module may be faulty, replace it.
•  *Check if the cable from touchpad to the main control module is faulty.  

  If it is a faulty cable, then the cable might have to be replaced.

Some zones cannot  

be turned off

•  Check if ‘Spill is activated’ is displayed on the LCD screen. 
•  Check if ‘Spill’ status is displayed for the Group status in the home  

  screen. Opening other zones will rectify the error 
•  *If all zones are turned on but the total opening percentage doesn’t  

  meet the required spill percentage, then the SPILL warning message  

  will be displayed. Increasing the opening percentage of a few zones  

  will resolve the issue.
•  *Check spill set-point.

No display on the LCD

•   *Check if the cable is plugged in properly. Unplug the cable and  

  reconnect it.
•   *Check if there is power to the unit.

LCD Display  

Corrupted

•  Reset LCD by holding RESET button at the bottom of the Touchpad for  

  2s.
•  *If error is still not resolved, reset touchpad by unplugging the cable  

  from behind and then reconnect it after a couple minutes. If the  

  corrupted display remains, power off/on the mainboard. Otherwise,  

  replace the touchpad.

Some zones are  

not operational

•   *Check Grouping and find out if the right zones have been assigned to  

  the right groups and have been turned ON/OFF in Zoning section.
•   *Check if the total group number and zone number are correct.
•   *Check if the LEDs on the main module light up for the relevant zones  

  when the zone dampers are turned On/Off. If there is no response,  

  there might be a faulty cable and the cable would have to be replaced.  

  If the zone is still non-functional then there might be a faulty damper  

  motor.

*:

 

These checks in the guide should be carried out by qualified personnel.  

 

If you have any doubt regarding the above please contact your installer.

Содержание ZoneMaser ZoneTouch V2

Страница 1: ...ZoneTouch V2 Zone Control System User Manual www polyaire com au 2014 Polyaire Pty Ltd...

Страница 2: ...ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM User Manual II...

Страница 3: ...p 7 5 User Settings 8 5 1 Time Date setup 8 5 2 Owner s Name 9 5 3 Turbo Group 9 5 4 Temperature Display 10 5 5 Touch Tone 10 6 Information Sheets 11 7 Troubleshooting Guide 14 8 Specifications 15 TAB...

Страница 4: ...nes automatically resume their original on off state once power is restored after power outage 1 A zone is the area where air supply is controlled by one motorized damper 2 A group is a few zones grou...

Страница 5: ...ouch tone status and ZoneTouch logo as shown in Figure 1 NOTE The touch screen will go to the sleep mode after 90 seconds of inactivity In sleep mode the screen is blank Touching any area of the scree...

Страница 6: ...p will open or close accordingly b The group status can be set to TURBO active when the group is specified as a turbo group refer to 5 3 and the grey turbo indicator will turn blue to indicate the TUR...

Страница 7: ...nt event time slots NOTE A group can have up to a maximum of 4 zones Your installer would have already set up your zones and groups 3 2 Adjusting airflow for a group The damper opening percentage for...

Страница 8: ...he home screen to enter Programming screen Figure 4 Figure 4 Figure 6 b Touch a day option radio button to select Monday Friday Saturday or Sunday program to modify Touch the time switch radio button...

Страница 9: ...uch the program field of a group to show all program options Figure 8 Touching a program option will assign the program to the group Figure 9 Each group can be assigned with one program from program1...

Страница 10: ...e Touching button will go back to the home screen from User setting pages Figure 11 Figure 12 5 User Settings Figure 13 Figure 14 5 1 Time Date setup a Touch on the User Settings screen Figure 12 to e...

Страница 11: ...l other groups dampers opening positions are reduced by 50 of their open percentage value This will bring a large volume of extra air into the designated area and cool or heat the area quicker Typical...

Страница 12: ...screen Below images show the enabled status Figure 17 and disabled status Figure 18 of temperature display 5 5 Touch Tone The touch tone feature allows to either enable or disable the tone when the s...

Страница 13: ...ormation Sheets These should be filled out by the installer Total Groups Bypass Damper Installed Supply Air Sensor Installed Yes No Yes No Group Group Name Zones Included Turbo Function 1 2 3 4 5 6 7...

Страница 14: ...ROL SYSTEM User Manual 12 Installer Contact Number Date Zone Balance Percentage Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone A Zone B Zone C Zone D Zone E Zone F Zone G Table 4...

Страница 15: ...Off time 2 Monday Friday Saturday Sunday Groups PROGRAM 2 On time 1 Off time 1 On time 2 Off time 2 Monday Friday Saturday Sunday Groups PROGRAM 3 On time 1 Off time 1 On time 2 Off time 2 Monday Fri...

Страница 16: ...the Group status in the home screen Opening other zones will rectify the error If all zones are turned on but the total opening percentage doesn t meet the required spill percentage then the SPILL war...

Страница 17: ...Altitude 0 to 2000 meters Operating relative humidity 10 to 80 Avoid static electricity hazards Avoid electromagnetic radiation sources Avoid dust contamination Avoid highly corrosive environments Zo...

Страница 18: ...ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM User Manual 16...

Страница 19: ...ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM User Manual 17...

Страница 20: ...ZMZT2_USER_V1 0 POLYAIRE PTY LTD 11 13 WHITE ROAD GEPPS CROSS SOUTH AUSTRALIA 5094 TEL 08 8349 8466 FAX 08 8349 8446 www polyaire com au...

Отзывы: