background image

A.  Testing Cleaner Head and Floating Cable

1. 

Set the cleaner head on a block of wood or some 
object that allows the cleaner wheels to be elevated 
from the surface.

2. 

Plug the Polaris Quick Diagnostic Test Box into a 
GFCI protected outlet.

3. Connect 

the 

fl

 oating cable from the cleaner to the 

test box (see Figure 2).

7. 

If the cycle completes without 

fl

 ashing lights, the 

fl

 oating cable and cleaner head have successfully 

passed the test. 

8. 

If the diagnostic box 

fl

 ashes red lights at any 

time during the test or the cleaner head does 
not activate, proceed to 

Section C: Diagnosing a 

Defective Motor Block or Floating Cable.

 

B.  Testing the Control Unit

1. 

Reconnect the cleaner to the customer’s control 
unit.  Press the Cycle I button. (see Figure 5).

Figure 2.  Connect Floating Cable to Test Box

Figure 4.  Checking for Air Flow

Figure 3.  Select the Cleaner Model

Figure 5.  Testing the Control Unit

4. 

Determine the corresponding button for the model 
being diagnosed (9300 or 9300xi).  Press the button 
to start the test (see Figure 3).

2. 

The drive cycle will turn on and will last for 
approximately 

fi

 ve (5) seconds. 

3. 

The cleaner will then drive forward for approximately 

fi

 ve (5) seconds.   If the cleaner does not drive 

forward for approximately 

fi

 ve (5) seconds, then the 

control unit is defective and must be replaced.

Page 2

5. 

The pump motor should start 

fi

 rst.  Check for air 

fl

 owing from the exhaust on the back end of the 

cleaner (see Figure 4).

6. 

Next, the drive motors should start within 

fi

 ve (5) 

seconds after the pump motor starts. Take note 
which direction the drive motors are rotating. The 
drive motors drive the two (2) front wheels. Verify 
that the two (2) front drive wheels move forward 
then in reverse.  After ten (10) seconds, all motors 
should stop. 

Содержание 9300

Страница 1: ... GFCI Such a GFCI receptacle should be provided by a qualified installer and should be tested on a routine basis To test the GFCI push the test button The GFCI should interrupt power Push the reset button Power should be restored If the GFCI fails to operate in this manner the GFCI is defective If the GFCI interrupts power to the pump without the test button being pushed a ground current is flowin...

Страница 2: ...ting Cable to Test Box Figure 4 Checking for Air Flow Figure 3 Select the Cleaner Model Figure 5 Testing the Control Unit 4 Determine the corresponding button for the model being diagnosed 9300 or 9300xi Press the button to start the test see Figure 3 2 The drive cycle will turn on and will last for approximately five 5 seconds 3 The cleaner will then drive forward for approximately five 5 seconds...

Страница 3: ...ace and remove the propeller guard see Figure 6 Figure 6 Remove the Propeller Guard Figure 8 Remove the Propeller Guard Figure 9 Remove the Floating Cable Figure 7 Remove the Propeller and Flow Director 2 Remove the propeller and the flow director see Figure 7 3 Close the cover and turn the cleaner over so that it s resting on its top 4 Remove the four 4 screws from the bottom of the cleaner Remov...

Страница 4: ...lashing red lights on the diagnostic panel then the motor block is defective Replace the motor block and return old motor to Zodiac 6 Using the short test cable connect the motor block to the Polaris Quick Diagnostic Test Box see Figure 10 7 Once secured start the diagnostic test see Figure 11 All trademarks referenced herein are the property of their respective owners ZODIAC is a registered trade...

Отзывы: