E30
Failure
report
Suction temp sensor 1
failure
Sensor short or open
Secure connector or replace sensor
E32
System
Shutdown
Low outlet water temp
protection
Outlet water temp lower than
setting
Check pipeline filter, valve and water pump
head
E35
System
Shutdown
Compressor 1 overcurrent
Compressor 1 current exceeds
setting
Check compressor current
E36
System
Shutdown
Compressor 2overcurrent
Compressor 2 current exceeds
setting
Check compressor current
E39
Failure
report
EEPROM error
Restore to factory settings
E50
E51
E52
E53
E54
Failure
report
Heating/cooling
:
after valve
sensor 1 failure
Hot water
:
Inlet water temp
sensor failure
Sensor short or open
Secure connector or replace sensor
E55
Failure
report
Heating/Cooling
:
after
valve sensor 2 failure
Hot water
:
N/A
Sensor short or open
Secure connector or replace sensor
E56
E57
E63
E65
E66
E67
E68
E72
E73
E76
E77
E78