Enter the Parameter Menu
1.
Unlock the control panel, if locked.
2.
Press and hold the SET
button until ‘
d1
’ flashes on the display.
3.
Press the SET
button repeatedly to scroll to the desired parameter (see below).
Manual Defrost
The appliance will automatically run a defrost cycle every six hours.
To manually defrost the appliance:
1.
Press and hold the DEFROST
button for 5 seconds.
2.
The defrost cycle will start immediately and the Defrost LED illuminates. The defrost will last a maximum of 30 minutes.
3.
Waste water is collected in the waste water tray.
Parameter
Name
Description
Range
d1
Operating temperature
Set the operating temperature of the appliance
-2°C to 10°C
d2
Temperature
Differential
The Temperature Differential is the allowed temperature difference above and below the
operating temperature before the compressor starts/cuts off
0 to 20°C
d3
Temperature Range
Set the minimum (d3) and maximum (d4) temperatures that the appliance can fluctuate
between
-40°C
d4
95°C
d5
Compressor Activation
Time Intervals
Enter the minimum time interval between the compressor turning off after turning on.
0-999 seconds
d6
Maximum Temperature
Differential Alarm
Set an alarm to sound if the temperature inside the appliance exceeds the set operating
temperature by a specified amount
0°C-50°C
d7
Temperature
Differential Alarm Delay Set a delay before the temperature differential alarm is triggered
0-99 minutes
d8
Defrost Cycle Time
Intervals
Set the time between each defrost cycle
1-999 hours
d9
Maximum Defrost
Duration
Set the maximum length of the defrost cycle
Note: The defrost duration can be overridden by parameter d10 (below), if the
cut-off temperature is reached before the end of the defrost duration
0-999 minutes
d10
Defrost Cut-off
Temperature
Set the defrost cut-off temperature
-45°C to 50°C
d11
Additional Cut-off
Defrost Period
Set an additional amount of defrost time after the defrost cut-off point has been reached (if
required)
0-99 minutes
d12
Delayed Actual
Temperature Display
Set the length of time the inner temperature of the appliance (before defrost started) is
displayed for after a defrost cycle has finished
0-99 minutes
d13
Compressor On/Off
During Defrost
Turn the Compressor On or Off during the defrost cycle
On (
1
) or Off (
0
)
d14
Evaporator Drying Time
Set the amount of time the compressor remains turned Off after a defrost cycle, reducing the
amount of frost build up
0-99 minutes
=
19
Temperature Offset
Should there be any variance between measured and actual temperature, the measured
temperature can be offset to compensate
-20°C to 20°C
=
22
Unit of Measurement
Set whether the temperature is displayed in Centigrade or Fahrenheit
Centigrade (
0
) or Fahrenheit (
1
)
=
23
Compressor Operation
During Probe Failure
Set whether the compressor runs or remains Off during a temperature probe failure
Compressor runs (
1
)
Remains Off until fault fixed (
0
)
Runs intermittently with
parameters =
24
and =
25
(
2
)
=
24
Compressor ‘On’
Duration
Set the length of time the compressor runs during a temperature probe failure
1-99 minutes
=
25
Compressor ‘Off’
Duration
Set the length of time the compressor remains Off during a temperature probe failure
1-99 minutes
=
34
Initial Defrost After
Startup
Set whether the appliance starts a defrost cycle 10 minutes after startup or after the time
programmed in parameter
d8
(Defrost Cycle Time Intervals)
Begins 10 minutes after startup
(
0
) or when programmed (
1
)
=
38
Minimum Temperature
Alarm
Set the display to flash should the inner temperature of the appliance drop beyond a specified
point from the programmed operating temperature
1°C to 50°C
Note: The cycle starts from the time the appliance is initially powered up.
Note: Starting a manual defrost also resets the automatic defrost timer.
The next automatic defrost will start six hours after the manual defrost has finished.