Page 11
When unit is turned on in heating mode:
a)
When
Tr ≤ Ts
- 1 ºC (Modbus 300033 setting), MTV1 and AUX2 are turned on. Fan is turned on at setting speed. DA1 is
at 10VDC for 2 minutes, then check Ti1:
If Ti1 < 28ºC (Modbus 300017 setting), EH is turned on. DA1 is at 10VDC.
If 28ºC<Ti1< 28 (Modbus 3000017 setting) +4ºC, EH is kept at original state. DA1 is at original state.
If Ti1 ≥ 28(Modbus 3000017 setting) + 4ºC, EH is turned off. DA1 output is based on water temperature difference (Ti1/Ti2)
and Modbus parameter 300027 setting PID calculation. The output is minimum output (Modbus300015 setting) ~10VDC.
If Ti1 sensor is damaged, fan will run at set speed.
b)
When Tr > Ts+1 ºC (Modbus 300033 setting), MTV1 and AUX2 are turned off. EH is turned off. DA1 is at 0VDC. fan is
turned on at low speed.
When unit is turned off, MTV1 and AUX2 are turned off. DA1 is at 0VDC. Fan is turned off after 2 minutes.
With Electrical Heater as primary heat source (Modbus300043=2)
When unit is turned on in heating mode: When
Ti2 ≤ 35ºC (or Ti2 is broken) and Tr ≤ Ts
- 1 ºC (Modbus 300033 setting), Fan is
turned on at setting speed, EH is turned on. When Tr > Ts + 1 ºC (Modbus 300033 setting), EH is turned off. Fan is turned on
at low speed.
When unit is turned off, EH is turned off. Fan is turned off after 2 minutes.
OVER-HEAT PROTECTION OF INDOOR COIL
If Ti1 ≥ 75ºC, then MTV1
, AUX2, DA1 and EH are turned off. Indoor fan remains on and runs at high speed.
If Ti1 < 70ºC, then unit keep original state.
If the indoor coil temperature sensor is damaged or not connected, the protection mode will be overridden and the unit
will work according to the pre-heat and post-heat program.
DEHUMIDIFICATION MODE
When unit is turned on in dehumidification mode:
a)
AUX1 is turned on. Ts is 24 ºC.
b)
If Tr ≥ 25ºC
for 30S, then MTV1 will be on for 3 minutes, and then off for 4 minutes. DA1 is on at 3 times of (Modbus
300016 setting). Fan is turned on at low speed.
c)
If 16ºC ≤ Tr < 25ºC
for 30S, then MTV1 will be on for 3 minutes, and then off for 6 minutes. DA1 is on at double of
(Modbus 300016 setting). Fan is turned on at low speed.
d)
If Tr < 16ºC for 30S, then MTV1 will be on for 3 minutes, and then off for 10 minutes. DA1 is on at (Modbus 300016
setting). Fan is turned on at low speed.
e)
At the end of the above dehumidification cycle, the system will decide the next dehumidification control option.
AUTO MODE
When unit is turned on in Auto mode, fan is turned on at setting speed for 30s, then check Tr and Ts:
If Ts
≥Tr+3 ºC, the unit runs in heating mode. If Tr
-3 ºC<Ts<Tr+3 ºC, the unit runs in fan mode. If Ts<Tr-3 ºC, the unit runs in
cooling mode. If unit working mode is confirmed, the unit will not change the working mode. After the unit is turned off and
restart in 2 hours, working mode will be confirmed again.
PRO INPUT FUNCTION
Standard Setting when the unit is on:
If PRO input is closed for 60S, the unit is turned off.
If PRO input is opened for 60S, the unit is turned on.
Other function can be set in Modbus.
2019-IOM-SWC-V-EC-I-001