POLA SC6D Скачать руководство пользователя страница 4

These settings refer  to the mode of operation of the  system and must be made on
initial start-up. Press  - / + together  for  at  least  one  second:
the message C.O.S.t.    will be displayed.
Press than repeatly ALARM until interested variable's message is displayed  (see
table below) : variable value and related message will be displayed.
Press + or - to set a new value and then ALARM to confirm.
The next system constant will then appear.
You can press ALARM for a least two second  to escape and return to the Run Mode.

*3) You can correct the readings on the sensor (or -).

*2) tEnP =1 ; °C   Temperature range.

*1) For more details see Operative Diagrams.

COST PROGRAMMING  (System costants)

HEATING OPERATIVE DIAGRAMS

AMBIENT PROBE TEMPERATURE

HEAT

 ON

 OFF

1/2 d.HEA 1/2 d.HEA

t.HEA

ALARM OPERATIVE DIAGRAMS

 ON

 OFF

t.AL.

MINIMUM ALARM

 ON

 OFF

MAXIMUM ALARM

t.AL.

d.HEA

tEnP =2 ;  °F   Temperature range.

In normal condition on display appears temperature.
Some special condition can cause following messages:

* In these cases alarm output relay is on.

SPECIAL MESSAGGES ON DISPLAY

When selected probe has
an open circuit wire failure.

*When selected probe has
a short circuit wire failure.

In some start-up conditions may be useful to work in "hand" mode.
Power off theprocessor, press + key and keep it pressed giving power on:
 HAnd  message will be displayed (release now   key).
Push  +  until is displayed number required to be handed:
= HEAT relay,   2 = Alarm relay.

Pushing again  +  for increase relay number previous relay is disactivated.
You can press ALARM for a least  two seconds to escape and return to the Run Mode.

HAND MODE

At delivery this processor is ready programmed with  the  following (variable)
settings. To return to these settings at any time:
Power off the processor, press ALARM key and keep it pressed giving power on:
boot  message will be displayed (release now ALARM key).
t.HEA = 20.0°         t.vEn = 25.0°         SP._ _= 0%       SP.- - = 100%

t.AL._ 10.0°         t. AL. - = 40.0       COST value are shown in COST paragraph.

PRESET PROGRAMS (bootstrap)

AMBIENT PROBE TEMPERATURE

Mess.

Value

Meaning

Note

d.HEA

0.2°

 ° HEAT differential

*1)

ProP

3.0°

 ° Ventilation proportional range

*1)

FrEo

=1

 Power line frequency    =1 ; 50Hz     =2 ; 60Hz

tEnP

=1

 Temperature representation (=1 °C,  =2 °F)

*2)

Ad.tE

 0.0°  ° Input sensor temperature correction (+ or -)

*3)

VENTILATION OPERATIVE DIAGRAMS

% Ventilation

ProP

 

0%

 

10%

 

20%

 

30%

 

40%

 

50%

 

60%

 

70%

 

80%

 

90%

 

100%

AMBIENT PROBE TEMPERATURE

Minimum and maximum speed

 are conditioned by these sets.

example with
SP._ _ = 10%

example with
SP. - - = 90%

t.vEn

Отзывы: