POLA HP59/W Скачать руководство пользователя страница 2

Mess.

Value

Meaning

Note

n.b.

1.0

  Neutral band (mmH 20).

*1

diF.P

0.2

  Pressure differential (mmH20).

*1

t.oF

2"

 Waiting time of actioning

*2

t.on

2"

 Working time of actioning

*2

IntE

1"

 Pressure reading integration time

ABLE

=1

 Key SET abilitation

*3

Ad.Pr

0.0

 Pressure sensor correction (+ o -)

"HAND MODE"

.

In some start-up conditions may be useful to work in "hand" mode.

Power off the processor, press + key and keep it pressed giving power on:

HAnd

  message will be displayed (release now  +  key).

Push  +  until is displayed number required to be handed(1= relay MIN,
 2=relay MAX) and push SET  for activing relay.
Pushing again  +  for increase relay number previous relay is disactivated.
You can press SET  for a least  two seconds to escape and return to the 

Run Mode.

These settings refer  to the mode operation of the system and must be made on
initial start-up.
Press  - / + together  for  at  least  one  second.
the message 

C.O.S.t.

  will be displayed.

Press than repeatly SETuntil interested variable's message is displayed  (see
table below) : variable value and related message will be displayed.
Press + or - to set a new value and then SET to confirm.
The next system constant will then appear.
You can press SET  for a least two second  to escape and return to the 

Run Mode

.

COSt PROGRAMMING

 

(System constants).

*1) For more details see 

Operative Diagrams.

*3) Key SET qualification:

=0

 key not able (pressing SET 

no-oP 

message will be displayed).

=1

 Key able.

STATE INDICATION LAMPS

.

L a m p .

A ct io n in g

N °   r ela y

H PA L   co n tact s

M IN

M IN  On   a ctionin g

RYA

3-4-5

M A X

M AX On ac tio ning

RYB

6-7-8

If 

t.Of and t.On time worked (see COSt), MIN and MAX lamp flash during the request of actioning, and

lighting during the action of the relay.

Swinging Ambient / Set temperature (t.SEt) indicator

OUTPUT MAX  ON

OUTPUT MIN  ON

diF.P

OPERATIVE DIAGRAM.

diF.P

 ON

 OFF

MAX

MIN

     ON

 OFF

MAX ON actioning
conditionated by
t.Of and t.On  time
(see  COSt).

MIN ON actioning
conditionated by
t.Of  and  t.On
time (see COSt).

IN-OUT DIFFERENCE
OF PRESSURE.

SEt.P

1/2 n.b.

1/2 n.b.

SEt.P

1/2 n.b.

1/2 n.b.

At delivery this processor is ready programmed with  the  following (variable)
settings. To return to these settings at any time:
Power off the processor, press SET key and keep it pressed giving power on:
when

 boot 

 full message will be displayed (release now SET key).  

SEt.P=

3.0

The COSt  values are shown in 

COSt Programming.

PRESET PROGRAMS (Bootstrap).

*2) When actioning is required  (MIN o MAX) , the request must remain for a higer

time than 

t.oF

, then come execute for the time

 t.On

 and again wait for the time 

t.oF

,

and so on until remain the request of actioning.
 With  

t.oF=0

 the request of actioning come execute without delay time.