OPERATIVE DIAGRAMS

These settings refer to the mode of operation of the system and must be made on
initial start-up. Press

- / +

together for at least one second:

the message

C.O.S.t.

will be displayed.

Press than repeatly

ALARM

until interested variable's message is displayed (see

table below) : variable value and related message will be displayed.
Press

+

or

-

to set a new value and then

ALARM

to confirm.

The next system constant will then appear.
You can press

ALARM

for a least two second to escape and return to the

Run Mode

.

VIEWING TEMPERATURE RECORDING

Press

+

:

will be displayed followed by

°Maximum Temperature Recording.

Press

-

:

will be displayed followed by

°Minimum Temperature Recording.

Values recorder are memory permanent stored: for memory clear keep pushed

+

keys for more than 3 seconds:

CLEA

message will be composed on display before

clearing operation.

COSt PROGRAMMING

(System constants)

*1)

For more details see

Operating Diagrams

.

*2)

Over this temperature

HEAT

and

DEHM

are Off (Max Heat On): in this condition lamps

HEAT

and

DEHM

are flashes.

*3)

Available only with

HPAL

optional slot.

Mess. Value

Meaning

Notes

r.HEA

-1.0°

° HEAT setting referring to t.SEt

*1)

r.COL

1.0°

° COOL setting referring to t.SEt

*1)

r.Hun

-5.0H

%RH HUM referring to H.SEt

*1)

r.dEH

5.0H

%RH DEHM referring to H.SEt

*1)

d.HEA

0.5°

° HEAT differential

*1)

d.COL

0.5°

° COOL differential

*1)

d.Hun

1.0H

%RH HUM differential

*1)

d.dEH

1.0H

%RH DEHM differential

*1)

t.HEA

25.0°

° Max Heat set (Max Heat On)

*2)

n.CHA

0

Daily number C.AIR

*3)

d.CHA

0'

Minutes dutation C.AIR

*3)

Huny

=1

Humidity sensor type

*4)

tEnP

=1

Temperature representation (=1°C, =2°F)

*5)

Ad.t1

0.0°

° Input ambient temperature correction (+ or -)

*6)

Ad.Hu

0.0H

%RH ambient humidity correction (+ or -)

*6)

Ad.t3

0.0°

° Input Max Heat temperature correction (+ or -)

*6)

Ad.t4

0.0°

° Input Aux temperature correction (+ or -)z

*6)

Huny =1

:

0-20mA

sensor (

RHP

type): direct connect.

Huny =2

:

4-20mA

sensor: to call for a

HALI

power pack.

*5)

tEnP =1

: ;

°C

Temperature range.

tEnP =2

;

°F

Temperature range.

*6

) You can correct the readings on the sensor (

+

or

-

).

*4) HP47

can be configurated in these different humidity sensor type:

ON

Condizionated
by

M AX

HEAT OF

HEAT

COOL

d.HEA

d.COL

t.SEt

- r.HEA

r.COL

1/ 2

1/ 2

1/ 2

1/ 2

ON

AMB. TEMP

ON

HUM

DEHM

d.Hun

d.dEH

H.SEt

- r.Hun

r.dEH

1/ 2

1/ 2

1/ 2

1/ 2

ON

HUM. TEMP

Condizionated
by

MAX

HEAT OF

Max H Off

MAX

HEAT

0.2°

Max H On

Max H. Temp

OFF

0.2°

ON

MIN

ALARM

OFF

MAX

ALARM

0.2°

ON

AMB. TEMP.

AL._ _

AL. - -

AMB. TEMP.

t.HEA

AIR-CHANGE

MINUTES

d.CHA

ON

24h /

n.CHA

In some start-up conditions may be useful to work in "hand" mode.

Power off theprocessor, press

+

key and keep it pressed giving power on:

HAnd

message will be displayed (release now

+

key).

Push

+

until is displayed number required to be handed (see table relays "

N° Relay

") and

push

ALARM

for activing relay.

Pushing again

+

for increase relay number previous relay is disactivated. You can press

ALARM

for a least two seconds to escape and return to the

Run Mode.

"HAND MODE"

At delivery this processor is ready programmed with the following (variable) settings.
To return to these settings at any time:
Power off the processor, press

ALARM

key and keep it pressed giving power on:

boot

message will be displayed (release now

ALARM

key).

t.SEt

=

10.0°

H.SEt

=

80.0H

AL. _ _

=

-50.0°

AL. - -

=

50.0°

PRESET PROGRAMS

COST

value are shown in

COST

paragraph.