Lam p.

State

N° Relay

Contacts

HEAT (*1)

HEAT On

1

3-4

CO OL

COOL On

2

5-6

HU M

HUM On

3

7-8

DEHM (*1)

DEHM On

4

9-10

MIN

MIN ALARM On (n.c.)

7 *

6-7-8 *

MA X

MAX ALARM On (n.c.)

7 *

6-7-8 *

C.AIR

CHANGE AIR On

6 *

3-4-5 *

IDEAL

Ok

temperature

STATE INDICATION LAMPS

The light situaded at the bottom of the display show the state of the various relays as set out below:

(

*

) Available only with

HPAL

optional slot.

(

*1

) Action light (

HEAT

-

COOL

) flash during delay time (see

COSt

function

t.on-t.Of

).

MAIN SETTING

(Run Mode)

Press

TEMP

(key lamp flashes):

this message will be displayed instead of the

°

Set temperature value

.

Press

+

or

-

to modify, press

TEMP

to confirm.

HUMIDITY SETTING.

Press

HUM

(key lamp flashes):

this message will be displayed instead of the

%RH Set Humidity value

.

Press

+

or

-

to modify, press

HUM

to confirm.

ALARM TEMPERATURE SETTING.

Press

ALARM

(key lamp flashes):

this message will be displayed instead of the

°

Set Minimum alarm temperature value

.

Press

+

or

-

to modify, press

ALARM

to confirm.

At this point:
this message will be displayed instead of the

° Set Maximum alarm temperature value

.

Press

+

or

-

to modify, press

ALARM

to exit.

TEMPERATURE AND PROGRAM STATE VIEWING

*1) This probe show only Aux. temperature.

With

TEMP

key lamp light (press

TEMP

key) ambient temperature is displayed.

With

HUM

key lamp light (press

HUM

) ambient humidity is displayed.

For viewing other parameters press these keys for at least two seconds:

Key

Message

Meaning

Notes

TEMP

t.AuS

° Aux Temp viewing

(*1)

HUM

t. - - -

° Max Heat viewing

ALARM

C.Air

C.Air minutes count down

not in C.AIR

"

On.C.A

C.Air end minutes

in C.AIR

"

-oF-

C.Air not active

TEMPERATURE SETTING

HP47

Thermal chamber controller

SL 2.0

Handbook

INSTALLATION

How to connect the sensors

Connect the sensor provided as shown in the diagram. For remote connections use a standard

0.5-square millimeter two-pole wire , taking great care

over the connections, by insulating and

sealing the joins carefully.

-O.C.-

is displayed when the temperature sensor wiring is open,

-S.C.-

is

displayed when the temperature sensor wiring is short circuit.

How to connect the contacts

Connect terminals on the terminal
block (contacts up to 4AMP.AC1)

How to connect the line

Connect 220V line on terminals

L-N

.

Protect supply with adequate fuse.

HP47

230V

 L

IN

E

 *

H

E

AT

 O

UT

P

UT

CO

O

L

 O

UT

P

U

T

DE

HM

 O

UT

P

UT

S

X

 AM

BI

E

NT

T

EM

PER

. PR

O

B

E

HUM

IDI

T

Y

 P

R

O

BE

HUM

 O

UT

P

UT

13 14

+

-

-

+

HALI

4-20mA

sensor probe connection

Power pack

4-20mA
sensor

13 14

RHP

+

-

RHP

sensor probe connection

S

X

M

AX

 H

E

AT

T

EM

PER

. PR

O

B

E

S

X

AU

X

IL

IA

RY

T

EM

PER

. PR

O

B

E

*

Other power voltage if you required

9

81

116

As it company policy to continually improve the products the Manufacturers

reserve the right to make any modifications thereto without prior notice.

They cannot be held liable for any damage due to malfunction.