FCC ID:

 M5ZANA 

 

Example: 
 

 

C1

283FA60B000000EC000F8AD0AB<CR> 

 

This field is the mode indicator, the LS-bit which indicates the 
service state of the transmitter, C1=normal, C0=service mode. 

 
 
C1

283FA60B000000EC

000F8AD0AB <CR> 

   This 

field 

is 

the 

unique 

serial number of the 1-Wire  sensor. 

 
 
C1283FA60B000000EC

000F

8AD0AB <CR> 

This is analog data field stored MSByte first as a 12-bit number in 
a 16-bit field.  The number shown is 000F (15) or 15/4096 of full 
scale.  If this is a 0-20 milliamp input this would be .07 MilliAmp.  
If the input is 0-5 Volts this would be 0.0183 Volts. 

 
C1283FA60B000000EC000F

8AD0

AB <CR> 

This field is the CRC-16 error check as was originally received and 
checked.  This CRC is over the first 11 bytes of the packet starting 
with the mode flags and ending with inclusion of the temperature 
data. 

 
C1283FA60B000000EC000F8AD0

AB

 <CR> 

This field is the mod 256 sum of all the ASCII character values in 
the response but does not include the <CR>. 
 

 

C828AE9105000000AA2D2DD474AB 

<CR> 

 

 

 

This is the CR terminator, 0Dhex.

 

 
 
 
 
 
 
 
 
 
 
 
 