7. Batteries contain hazardous voltage and current. Battery maintenance such as the battery replacement 

must be carried out by qualified personnel who are knowledgeable about batteries. No other persons should 

handle the batteries. 

 

5. Troubleshooting 

 

The following messages are the messages that users would find on UPS when it meets some problem, 

with the use of such messages, users can know where the problems are and how to deal with such 

problems. 

 

  Fault indicator on, indicates UPS has detected some fault. Buzzer beeps, indicate UPS need to be paid 

attention to. 

 Several fault indicators and status indicators on, are to help the user to diagnose fault. 

 

Problem 

Possible cause 

Solution 

The #1 fault LED and the #6 

LED are turned on, the 

buzzer beeps continuously 

The UPS shutdown due to 

internal overheat 

Make sure the UPS is not overloaded; the air 

vents are not blocked and the ambient 

temperature is not too high. Wait for 10 

minutes for the UPS to cool down before 

turning on again. If failed, please contact the 

distributor or service center. 

The #1 fault LED and the #2 

and #5 LED are turned on, 

and the buzzer beeps 

continuously 

The UPS output is short 

circuited. 

Turn off the UPS. Remove all the loads. 

Ensure that the load is not failed or the UPS 

has no internal faults before turning it on 

again. If failed, please contact the distributor or 

service center. 

The #1 fault LED and the #4 

LED are turned on, the UPS 

beeps continuously 

The UPS shuts down due 

to its internal fault. 

Please contact the distributor or service 

center. 

The #1 fault LED and the #5 

LED are turned on, the UPS 

beeps continuously 

The UPS shuts down due 

to its internal fault. 

Please contact the distributor or service 

center. 

The #1 fault LED and the #3 

LED are turned on, the UPS 

beeps continuously 

Overcharging protection 

The charger of the UPS is failed. Please 

contact the distributor or service center. 

The utility power LED flashes  The voltage or frequency of 

the utility power is out of the 

input range of the UPS 

The UPS is running in battery mode. To save 

your data and close the application program. 

Make sure the utility power is within the input 

voltage or frequency range permitted by the 

UPS. 

The #1 fault LED and the #2 

LED are turned on, the UPS 

beeps continuously 

The UPS is overloaded or 

the load equipment is faulty 

Check the loads and remove all non-critical 

equipment. Recalculate the load power and 

reduce the number of loads connected to the 

UPS. Check that the loads are not failed. 

PDF 

文件使用

 "pdfFactory Pro" 

试用版本创建

 

www.fineprint.cn

Содержание H1KS

Страница 1: ...1 H series online UPS LED 1 3KS L U U Us s se e er r r s s s m m ma a an n nu u ua a al l l PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...

Страница 2: ...ple Don t open the battery or do the battery damage for the liquid spilled from battery is strongly poisonous and do harmful to body Please avoid short circuit between battery anode and cathode otherwise this will cause electric shock or fire Don t dismantle the UPS cover there is danger of electric shock Don t touch batteries Batteries are not isolated with the input circuit there is high voltage...

Страница 3: ... 2 2 Safety notes 9 2 3 The description of front panel and display lamp 11 2 4 UPS input connection 11 2 5 UPS output connection 12 2 6 External battery connection 13 3 Operation and operating mode 14 3 1 Operation 14 3 2 Operating mode 15 4 Notes for battery disposal and battery replacement 19 5 Troubleshooting 20 Appendix The corresponding form of the LED display 22 Appendix 2 EMC grade standard...

Страница 4: ...eamlessly and provide alarm Advanced voltage compensation technology makes the wide input voltage range reducing the battery usage enhancing the adaptive ability against the bad mains power variation Advanced wide frequency input technology Wide input frequency range of UPS gives UPS a good compatibility with generator under field circumstances The advanced PFC technology on the input of UPS impro...

Страница 5: ...g current from the utility power to direct current This direct current charges the batteries and powers the inverter On the basis of this DC voltage the inverter generates a pure sinusoidal AC voltage which is constantly powering the loads Computers and peripherals are thus powered entirely by the UPS In the event of power failure the maintenance free batteries power the inverter This manual is ap...

Страница 6: ...lternating current source AC Direct current source DC Protective ground Alarm silence Overload indication Battery check Recyclable Do not dispose with ordinary trash 1 4 Appearance Front display panel PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...

Страница 7: ...H2 3KS rear panel EXT BATTERY COMPUTER INTERFACE INTELLIGENT SLOT BREAKER NETWO RK FAX M ODEM SUGERPROTECTION OUT IN OUTPUT FAN INPUT OUT IN H1KL rear panel PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...

Страница 8: ... 30A Power rating 1KVA 0 7KW 2KVA 1 4KW 3KVA 2 1KW Voltage 220VAC 1 2 Output Frequency 50 60Hz 0 2 Batteries number and type 3 12V7AH None 8 12V7AH None 8 12V7AH None 1 5 2 Dimensions and weights Model H1KS H1KL H2KS H2KL H3KS H3KL Dimensions W H D mm 145 400 220 192 460 340 192 460 340 Net weight 14 7 34 13 5 34 14 2 Installation 2 1 Unpacking and inspection PDF 文件使用 pdfFactory Pro 试用版本创建 www fin...

Страница 9: ...ipment 2 2 Safety notes 1 Keep good air circulation around UPS and far away from water flammable gas and corrosive 2 Don t place UPS on the slope and there should keep good air circulation between in vent on front panel bottom and fan out vent on back panel 3 The environment temperature around UPS should keep in a range of 0 40 4 There will be phenomena of condensing if the equipment is dismantled...

Страница 10: ...10 PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...

Страница 11: ...t power cable please use suitable socket with over current protection The rating for H1KS L should be above 6A for H2KS L should be above 12A for H3KS L should be above 16A UPS input connection PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...

Страница 12: ...PS output connection 2 6 External battery connection 1 Choose correct battery voltage according to the model The batteries can t be more or less connected otherwise UPS will work abnormal or be damaged Battery voltage for H1KL is 36VDC for H2KL is 96VDC for H3KL is 96VDC 2 One end of external battery cable is connected to UPS the other end is open style two cables used to connect to battery pack T...

Страница 13: ...y use of internal battery models A When you operate first time please open the battery breaker cover plate and turn on the battery breaker Then close the battery breaker cover plate B After you make sure that the power supply connection is correct set the input breaker in the ON position first At this time the fan rotates and the UPS supplies power to the load via the bypass The UPS operates in by...

Страница 14: ...ply and the UPS will perform self diagnosis finally not any display is shown on the display panel and no voltage output is available from the UPS output 3 1 4 Turn off the UPS with no utility power supplied in battery mode A Press the OFF button continuously for more than 1 second to power off the UPS B When being powered off the UPS will perform self diagnosis the load battery level LEDs will be ...

Страница 15: ...ned on then the loads can be connected to the UPS one by one l The power capacity of the AC generator should be at least twice of the UPS capacity 3 2 2 Battery mode The display panel in battery mode is shown in the following diagram Fig 3 2 The battery LED and the INV LED are turned on The displayed number of the battery level LEDs will be turned on in accordance with the battery capacity Note th...

Страница 16: ...ss mode l The utility power LED flashes It shows that the voltage or frequency of the utility power has exceeded the normal range of the UPS Fig 3 3 UPS bypass mode diagram l Other indications on the display panel are the same in utility mode l The UPS does not have the backup function when it is in bypass mode The power used by the load is supplied from the utility power via internal filter 3 2 4...

Страница 17: ...istributor for further information RS232 Interface The following are the descriptions and pin assignment of RS232 DB 9 port Baud rate 2400bps Data bit 8 bit Ending bit 1 bit Parity bit none DB 9 pin assignment Pin number Function description I O 3 Rx Input 2 Tx Output 5 Ground GND Optional AS400 interface This optional AS400 card provides dry contact closure signal OPEN or CLOSE RS232 Interface PD...

Страница 18: ...ons of hot climates the battery should be charged and discharged every 2 months The standard charging time should be at least 12 hours l Under normal conditions the battery life lasts 3 to 5 years In case if the battery is found not in good condition earlier replacement should be made Battery replacement should be performed by qualified personnel l Replace batteries with the same number and same t...

Страница 19: ...The charge time of standard units must be more than twelve hours 1 If it is necessary to replace any connection cables please purchase the original materials from the authorized distributors or service centers so as to avoid overheat or spark resulting in fire due to insufficient capacity 2 Do not dispose of batteries or battery packs in a fire they may explode 3 Do not open or mutilate batteries ...

Страница 20: ...ircuited Turn off the UPS Remove all the loads Ensure that the load is not failed or the UPS has no internal faults before turning it on again If failed please contact the distributor or service center The 1 fault LED and the 4 LED are turned on the UPS beeps continuously The UPS shuts down due to its internal fault Please contact the distributor or service center The 1 fault LED and the 5 LED are...

Страница 21: ... and remove the non critical equipment Battery discharging time diminishes Battery aged Replace the batteries Please contact the distributor to obtain the parts and replacement service The ON button is pressed too briefly Press the ON button for more than 1 second The UPS is not connected to the battery or the battery pack voltage is too low Check the battery or recharge the battery The UPS cannot...

Страница 22: ...40 Battery capacity Beep once every 4 sec 8 41 60 Battery capacity Beep once every 4 sec 9 61 80 Battery capacity Beep once every 4 sec 10 Battery mode 81 100 Battery capacity Beep once every 4 sec 11 Bypass mode Beep once every 2 min 12 Overloaded in utility mode and UPS still in INV mode Beep twice every sec 13 Overloaded in utility mode and UPS still in bypass mode Sustained beep 14 Utility pow...

Страница 23: ...usly beep 22 Battery voltage abnormal 23 BAT SCR failed Continuously beep 24 Fan abnormal Continuously beep 25 Bypass STS failed Sustained beep 26 INV RLY failed Sustained beep 27 Communication abnormal Sustained beep Solid ON Flash LED display and alarm warning are dependent on other conditions Appendix 2 EMC grade standards H series UPS are manufactured according to the following EMC internation...