DES-P Digital Engine Supervisor
Cat_DES-P-09-GSM new Ver 2.0
Page
6/9
9.1
Parameter Mode
Sl.
No
Display
Explanation of parameter
Factory
setting
Setting Range
1 Engine
Max
RPM
Max. permissible RPM, above this the
RPM is treated unhealthy & the
Generator is stopped.
1650 300-3000
2 Engine
O/RPM
Delay
The time for which the Generator RPM
should, continuously be unhealthy to
generate a fault condition.
10Sec 1-999
Sec.
4 Engine
Vbelt
RPM
Max. permissible Vbelt RPM, above this
the RPM is treated unhealthy & the
Generator is stopped.
300 300-600
5
V belt Delay
The time for which the Vbelt RPM
should, continuously be unhealthy to
generate a fault condition.
10Sec 1-999
Sec.
6 Available
Sensor
This select the installed sensors in the
Gensets. The display shall only display
the parameters for the sensor installed
and uninstalled sensor data shall not be
displayed. The protection for the function
with no measurement sensor installed
shall be through switch. Eg. If Oil
pressure sensor is not installed the unit
shall provide protection for LLOP
through oil pressure switch and not
through the oil pressure sensor (linear
measurement)
All sensors
All sensors,
Fuel &HWT,
Fuel & LLOP,
LLOP & HWT,
Fuel Only,
HWT Only,
LLOP Only,
No sensor
7
Fuel Level in %
Level of fuel at which the Engine shall
shut down
11% 10-100%
8
Low Lube
Pressure
Level of LLOP at which the Engine shall
shut down
1.0 Kg
/Cm2
0-8.5 Kg /Cm2
9 High
Water
Temp
Temperature of water at which the
Engine shall shut down
95
0-150
Degree centigrade
10
Sensor Type
Select sensor as in accordance with enine
A A,B
11
Fuel << delay
Monitoring time of Fuel Fault
5 Sec
1-999Sec
12
LLOP delay
Monitoring time of LLOP Fault
5 Sec
1-999 Sec
13 HWT
delay
Monitoring time of HWT Fault
5 Sec
1-999 Sec
14 Rad.
Water
Delay
Time for which Radiator water level has
to be active before issuing shut down
command
5 Sec
1-999 Sec
15 Hooter
Reset
Time/
Heater On time
Time for which the Hooter is active if not
reset manually/ Time for which heater is
to be switched on before crank
30 Sec
1-999Sec
16
Stop Sol On
Time
Time for which the fuel solenoid is
activated for shutting the engine
20Sec 1-100Sec
17
Gen Pick Up
Vol
Voltage of generator above which the
generator is assumed to be ON.
100V 80-150V
18 Service
Time
Hr
Time, in hours, after which the service is
due.
250Hrs 1-999
Hrs