DES-P Digital Engine Supervisor 

 
 

Cat_DES-P-09-GSM new Ver 2.0 
  

Page 

6/9 

 

9.1

 

Parameter Mode 

 

Sl.
No 

Display 

Explanation of parameter 

Factory 
setting 

Setting Range 

1 Engine 

Max 

RPM 

Max. permissible RPM, above this the 
RPM is treated unhealthy & the 
Generator is stopped. 

1650 300-3000 

2 Engine 

O/RPM 

Delay 

The time for which the Generator RPM 
should, continuously be unhealthy to 
generate a fault condition. 

10Sec 1-999 

Sec. 

4 Engine 

Vbelt 

RPM 

Max. permissible Vbelt RPM, above this 
the RPM is treated unhealthy & the 
Generator is stopped. 

300 300-600 

V belt  Delay 

The time for which the Vbelt RPM 
should, continuously be unhealthy to 
generate a fault condition. 

10Sec 1-999 

Sec. 

6 Available 

Sensor 

This select the installed sensors in the 
Gensets. The display shall only display 
the parameters for the sensor installed 
and uninstalled sensor data shall not be 
displayed. The protection for the function 
with no measurement sensor installed 
shall be through switch. Eg. If Oil 
pressure sensor is not installed the unit 
shall provide protection for LLOP 
through oil pressure switch and not 
through the oil pressure sensor (linear 
measurement) 

All sensors 

All sensors, 
Fuel &HWT, 
Fuel & LLOP, 
LLOP & HWT, 
Fuel Only, 
HWT Only, 
LLOP Only, 
No sensor 

Fuel Level in % 

Level of fuel at which the Engine shall 
shut down 

11% 10-100% 

Low Lube  
Pressure 

Level of LLOP at which the Engine shall 
shut down 

1.0 Kg 
/Cm2 

 0-8.5 Kg /Cm2 

9 High 

Water 

Temp  

Temperature  of water at which the 
Engine shall shut down 

95 

    0-150            
Degree centigrade 

10 

Sensor Type 

Select sensor as in accordance with enine 
 

A A,B 

11 

 Fuel << delay 

Monitoring time of Fuel Fault 

5 Sec 

1-999Sec 

12 

LLOP delay 

Monitoring time of LLOP Fault 

5 Sec 

1-999 Sec 

13 HWT 

delay 

 

Monitoring time of HWT Fault 

5 Sec 

1-999 Sec 

14 Rad. 

Water 

Delay  

Time for which Radiator water level has 
to be active before issuing shut down 
command 

5 Sec 

1-999 Sec 

15 Hooter 

Reset 

Time/ 
Heater On time  

Time for which the Hooter is active if not  
reset manually/ Time for which heater is 
to be switched on before crank 

30 Sec 

1-999Sec 

16 

Stop Sol On 
Time 

Time for which the fuel solenoid is 
activated for shutting the engine 

20Sec 1-100Sec 

17 

Gen Pick Up 
Vol 

Voltage of generator above which the 
generator is assumed to be ON.  

100V 80-150V 

18 Service 

 

Time 

Hr 

Time, in hours, after which the service is 
due. 

250Hrs 1-999 

Hrs 

Содержание Procom DES-P

Страница 1: ...organization Works Unit1 E 41 5 Okhla Industrial Area Phase II New Delhi 110020 Unit2 T 13 Okhla Industrial Area Phase II New Delhi 110020 Ph 011 30883538 41 9810344265 9310883837 Fax 0 1130883536 Em...

Страница 2: ...DES P Digital Engine Supervisor Cat_DES P 09 GSM new Ver 2 0 Page 2 9...

Страница 3: ...nnunciations 5 0 Contacts 6 0 Timers 7 0 Switches Description 8 0 Operation 9 0 Setting Procedure 9 1 Parameter Settings 9 2 Fault History Viewing 9 3 Service Hour Resetting 9 4 Programming Solenoid M...

Страница 4: ...acts for system stability and reliability All contacts are protected by TVS to strengthen the EMI EMC capabilities of the unit Housed in 92X92mm Din Standard housing 2 0 Protection Supervision Salient...

Страница 5: ...f 1 Sec shall reset both 5 R Programming Mode Entry Press R Key and than press while the R Key is pressed to enter the programming mode 8 0 Operation DES P is an engine monitoring and supervisor unit...

Страница 6: ...sure switch and not through the oil pressure sensor linear measurement All sensors All sensors Fuel HWT Fuel LLOP LLOP HWT Fuel Only HWT Only LLOP Only No sensor 7 Fuel Level in Level of fuel at which...

Страница 7: ...Service Hours Service due warning is issued by DES P by flashing the Ser LED This LED shall keep flashing till it is not reset by entering this mode Pls refer Para 9 for procedure to reset service hou...

Страница 8: ...1 Auxiliary supply ve 12 Crank NO Contact 13 Solenoid NO Contact 14 Charging Alternator On 15 Hooter 16 Common for All Contacts 17 Remote Start 18 Remote Stop 19 Not Connected 20 Not Connected 21 Not...

Страница 9: ...8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Not Connected Not Connected Not Connected Not Connected Oil Pressure Sensor Switch Water Temp Sensor Switch Low Fuel Sensor Switch RWL Switch Ch Alt Ve W...

Отзывы: