15
4.5.6
Connection with ecoMAX860P2,
D2
5.
Controller module can supply up
to 2 colored TOUCH type panels
simultaneously.
If the boiler controller is equipped with a
standard control panel (version with a knob),
two ecoSTER TOUCH room panels can be
supplied directly from the controller module
(
socket G4
). Third panel has to be supplied
by the additional power adapter
+12V
,
I≥0.5A
.
If the boiler controller is equipped with
ecoTOUCH control panel (colored with a
touch panel), only one ecoSTER TOUCH room
panel can be supplied directly from the
controller module (
socket G4
). Panels 2 and
3 have to be supplied by the additional
power adapter
+12V
,
I≥0.5A
.