Mixer settings without weather sensor
It  is  required  to  set  manually  desired 
temperature  in  mixer’s  heating  cycle  using 
parameter  Preset  mixer  temperature,  e.g. 
50ºC.  Such  should  be  a  value  to  provide 
required room temperature. 
After connecting a room thermostat, value of 
decline  in  preset  mixer  temperature  from 
thermostat should be set. (parameters Mixer 
room thermostat,
 e.g. 5ºC. This value should 
be 

chosen 

experimentally. 

room 

thermostat  can  be  a  traditional  one  or  a 
room  panel.  After  activating  the  thermostat, 
mixer  preset  temperature  will  be  reduced. 
When  this  value  is  reduced  correctly  then 
room temperature increase will be stopped. 
 
Mixer  settings  with  weather  sensor, 
without room panel

Set  parameter  Mixer  weather  control  in 
position  on.  Adjust  weather  curve  according 
to  point  8.18.  Using  parameter  Curve  shift 
set  required  room  temperature  according  to 
formula: Required room temperature = 20°C 
+ heating curve shift. In this configuration a 
thermostat  can  be  connected.  It  will  level 
inaccuracy  of  heating  curve  adjustment  in 
case  when  its  value  will  be  too  big.  In  such 
case value of decrease of preset mixer room 
temperature  from  thermostat  should  be  set 
i.e.  for  2°C.  After  disconnecting  thermostat 
plugs preset mixer cycle temperature will be 
reduced.  By  correct  adjustment  of  this 
reduction  will  stop  temperature  increase  of 
temperature in heated room.  
 
Mixer  settings  with  weather  sensor  and 
room panel
. 
Set  parameter  Mixer  weather  control.  In 
position  off.  Adjust  weather  curve  according 
to  point  8.18.  Room  panel  automatically 
moves  the  heating  curve  depending  on 
preset  room  temperature.  The  controller 
relates  adjustments  to  20

º

C,  i.e.  for  preset 

room  temperature  =  22

º

C  the  controller  will 

move  heating  curve  by  2

º

C,  for  preset  room 

temperature  =  18

º

C  the  controller  will  move 

heating  curve  by  -2

º

C.  In  some  cases 

described in point 8.18 it can be necessary to 
adjust heating curve shift. 

In this configuration room thermostat is able 
to: 
-  reduce  temperature  of  heating  cycle  by  a 
constant  value,  when  preset  temperature  in 
a  room  will  be  reached.  Similarly like  it  was 
described 

in 

previous 

point 

(not 

recommended), or  
-  automatically,  constantly  correct  heating 
cycle temperature.   
It  is  not  recommended  to  use  both  these 
possibilities at the same time.  
Automatic correction of room temperature is 
done according to formula: 
Correction  =  (preset  room  temperature  – 
measured  room  temperature)  x  room 
temperature factor / 10 
Example:  
Preset  temperature  in  heating  room  (set  in 
room  panel)  =  22ºC.  Measured  temperature 
in  room  (using  room  panel)  =  20ºC.  Room 
temperature factor
 = 15 
Preset  mixer  temperature  will  be  increased 
by  (22ºC  –  20ºC)  x  15/10  =  3ºC.  Correct 
value  of  parameter  must  be  found  room 
temperature  factor.  The  bigger  value  of 
factor  the  bigger  correction  of  preset  boiler 
temperature  factor.  When  set  on  value  “0” 
preset  mixer  temperature  is  not  corrected. 
Attention:  setting  too  high  value  of  room 
temperature  factor  may  cause  cyclic  room 
temperature fluctuations. 

8.18

 

 Weather control 

Depending 

on 

measured 

outside 

temperature, automatically controlled can be 
either  preset  boiler  temperature  and  mixer 
cycles  temperatures.  By  correct  adjustment 
of  heating  curve  temperature  of  heating 
circuits  is  counted  automatically  depending 
on value of external temperature.  Thanks to 
that  by  choosing  proper  heating  curve  for 
given  building,  room  temperature  remains 
approximately  the  same  –  no  matter  what 
outside  temperature.  Attention:  in  the 
process  of  experimental  adjustment  of 
proper  heating  curve  it  is  necessary  to 
temporarily  exclude  the  influence  of  room 
thermostat  on  the  controller’s  operation, 
irrespectively 

if 

room 

thermostat 

is 

connected  or  not,  by  setting  parameter: 
Mixer  1  settings 

  Mixer  room 

Содержание ecoMAX920P1-S TOUCH

Страница 1: ...TALLATION AND OPERATING MANUAL ISSUE 1 0_EN Functions available in additional module B ecoSTER TOUCH ecoNET300 ecoNET apk ecoNET app www econet24 com Devices are not standard equipment of the controll...

Страница 2: ...eam condensation conditions and cannot be exposed to water MAIN PRINCIPLES OF PROPER BOILER OPERATION WITH INDIVIDUAL FUZZY LOGIC The controller must be programmed individually for a given boiler and...

Страница 3: ...ROTECTION LEVEL 24 12 5 ELECTRIC CONNECTION 24 12 6 ELECTRIC SCHEME 26 12 7 CONNECTION OF TEMPERATURE SENSORS 28 12 8 CONNECTING THE WEATHER TEMP SENSOR 28 12 9 CONNECTING THE EXHAUST TEMPERATURE SENS...

Страница 4: ...is intended for boiler manufacturers Before applying the controller a boiler manufacturer should check if the controller s matching with the given boiler type is proper and whether it can cause dange...

Страница 5: ...bserve these instructions 4 Storage of documentation This assembly and operation manual as well as any other applicable documentation should be stored diligently so that it was available at any time I...

Страница 6: ...6...

Страница 7: ...USER SETTINGS ecoMAX920P1 S TOUCH...

Страница 8: ...n Decrease value Schedule Night time circ pump decrease Summer Winter SUMMER mode Summer Winter Auto SUMMER mode activation temp SUMMER mode deactivation temp Mixer 1 5 settings 5 Preset mixer tempera...

Страница 9: ...10 Functions affecting preset boiler temperature Following symbols signal respectively room thermostat contacts open preset room temperature reached preset boiler temperature decrease due to activated...

Страница 10: ...er e g boiler inactivity period in STOP mode Fan is switched on with the power set by Firing up airflow parameter Small fuel dosage is given 20 of basic dosage If during period set by Ignition test ti...

Страница 11: ...teresis H2 and 30 H1 hysteresis Hysteresis H1 and H2 of power modulation Operation in Fuzzy Logic mode In Fuzzy Logic mode the controller automatically regulates burner power to allow boiler operation...

Страница 12: ...ng the fuel and performs cyclic blowing according to Blowing time and Blowing pause settings in order to burn the remaining fuel After flame brightness dropping below Burning out end threshold value i...

Страница 13: ...the menu Summer Winter SUMMER mode for Summer Attention when boiler operates without heating buffer and the controller is switched into SUMMER mode than Standard mode operation is recommended It is no...

Страница 14: ...m temperature 18 C the controller will move heating curve by 2 C In some cases described in point 8 18 it can be necessary to adjust heating curve shift In this configuration room thermostat is able t...

Страница 15: ...oiler Time periods allow setting temperature reduction in given time period i e at night or when user leaves the heated room Thanks to it preset temperature can be reduced automatically without loss o...

Страница 16: ...Fuel level 0 There is a possibility to skip the calibration process if the parameters are set correctly Feeder efficiency and Capacity of tank which are in Service settings Burner settings Operation 8...

Страница 17: ...er operation status alarms allows to set controller parameters and its operation modes it also serves as an additional panel controlling the boiler 8 26 Cooperation with internet module The controller...

Страница 18: ...18...

Страница 19: ...19 INSTALLATION AND SERVICE SETTINGS ecoMAX920P1 S TOUCH...

Страница 20: ...c If the return sensor is clip on insulate it thermally from the surroundings and improve thermal contact with the pipe by using thermal grease Boiler s preset temperature must be set high enough to p...

Страница 21: ...te 80 C Boiler settings Minimum boiler temperature 75 C Service settings Boiler settings CH pump activation temperature 55 C Service settings CH and HUW settings Buffer support Yes Service settings Bu...

Страница 22: ...gs Buffer settings Buffer loading start temperature 50 C Service settings Buffer settings Buffer loading end temperature 75 C Service settings Buffer settings Mixer 1 2 3 4 support CH on Service setti...

Страница 23: ...ontroller 5 IP20 from the front side of the executive module IP00 from the side of the executive module cover against damage to the STB capillary placed in the terminal box 12 Controller installation...

Страница 24: ...ction device RCD with inrush current I n 30 mA protecting against the effects of the regulator including protection against fire After deactivating the controller there still can be a dangerous voltag...

Страница 25: ...from the casing of the controller as shown below Cables secured from splitting should be connected to screw terminals of the 6 connector Cables should be put through cable outlets in the casing 1 and...

Страница 26: ...otor AS ash removal servomotor RT room panel or ISM radio module Lambda probe module B module to support additional heating circuits BT boiler temp sensor type CT4 FS feeder temp sensor type CT4 RS bo...

Страница 27: ...rcuit temp sensor type CT4 T3 buffer upper temp sensor type CT4 T4 buffer lower temp sensor type CT4 LS fuel level sensor cooperating with bunker feeder T standard mixer room thermostat H voltage outp...

Страница 28: ...between these wires should be 100 mm Do not allow sensor wires to contact hot parts of the boiler and heating system Wires of temperature sensors are heat resistant to the temperature not exceeding 1...

Страница 29: ...2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S Pt1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8...

Страница 30: ...al module B Exemplary wiring diagram for connecting auxiliary boiler to the controller 1 additional module B 2 auxiliary boiler gas or oil 3 relay RM 84 2012 35 1006 and base GZT80 RELPOL By standard...

Страница 31: ...enu Service settings Boiler settings Auxiliary boiler and set zero value for its switching on temperature Exemplary external alarm device connection 1 additional module B 2 external alarm device 3 rel...

Страница 32: ...s power indicator of valve opening has been calibrated Attention in mixers 2 3 4 5 the calibration is automatic after switching on the mains power In case of these mixers wait until indicator of valve...

Страница 33: ...hich is not the controller s equipment Connect D D wires to G3 socket in the controller Maximum cables length to room panel depends on wires cross section and for 0 25 mm2 wire it should not exceed 30...

Страница 34: ...wer increasing Stoker emptying time Cycle Poker operation time Poker pause Stoker emptying time Roto Poker operation time Poker pause Stoker emptying time Cycle x K Poker operation time Poker pause Po...

Страница 35: ...ing start temperature Buffer loading end temperature Mixer 1 5 settings Thermostat selection Mixer support OFF CH ON Floor ON Only pump Minimum mixer temperature Maximum mixer temperature Proportional...

Страница 36: ...ng the fuel Feeder 2 minimum time Minimum operation time for feeder placed in burner Feeder 2 operation time Determines operation time of additional feeder bunker feeder The feeder is connected to add...

Страница 37: ...ted after finishing of which it will start operation again increasing the device s power to preset operation conditions Mechanism 2 when the burner finishes its operation in Burning out Burning off mo...

Страница 38: ...lt in excessive CH installation cooling since with such settings CH pump is off CH pump standstill parameter during HUW loading prevents it by enabling periodical CH pump activation during loading of...

Страница 39: ...eset temperature the supply of mixer pump will be off After decreasing circuit temperature by 2 C pump is switched on again This option is usually used to control floor heating pump when it cooperates...

Страница 40: ...ue to 0 switches alarm off Outputs test time After this time all devices that were switched ON in Manual control menu will be switched off automatically Show advanced Available options YES displays hi...

Страница 41: ...lame striking back will be off in this case Protective function against flame strike back does not work when feeder sensor is disconnected or when it s damaged or when the controller is not supplied T...

Страница 42: ...the form of two files file with panel program and a file with program for module A of the controller Place new firmware directly on the memory card do not place data in a folder Then connected electri...

Страница 43: ...necessary information read from nameplates In case of the controller it is essential to know its serial number If the serial number is unknown provide its model design and year of production Controlle...

Страница 44: ...and the fuel is not provided check the feeder according to its manual Fuel feeder not operating does not provide fuel Check if feeder wires are correctly connected to terminals If STB temperature lim...

Страница 45: ...45...

Страница 46: ...46...

Страница 47: ...47...

Страница 48: ...48 ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www plum pl National Waste Disposal No 000009381...

Отзывы: