Stealth installation
Stealth installation guide
Also applicable to: , Stealth M, Stealth M+
Be aware:
The Stealth is specifically designed
to be built in to an appliance/lighting
fixture or as a permanently connected
device in the electrical installation of
a building. Installation should always
be executed by a registered installer
in compliance with the local electrical
code (e.g. BS 7671 or NEC).
It is required to include an overcurrent protective device (circuit breaker),
that support a maximum rating of 16A (depending on your localisation). Be
sure to switch off the circuit before installing the Stealth!
The product should be installed in a closed flame retardant casing with a
proper strain-relief mechanism.
Use the L↑ labelled clamp to connect the phase wire to the appliance and
connect the neutral wire to one of the ‘N’ labelled clamps. Then connect
the incoming phase wire to the clamp labelled ‘L’ and the neutral wire to
the free ‘N’ connection.
For double phase 230V networks the second phase can be connected to the ‘N’ poles
(it will not be switched).
Information for the installer
Technical details
Voltage: 100-240 V~
Frequency: 50 / 60 Hz Total max. current: 16 A*
If a normal Stealth with relay is used, these additional maximum ratings apply:
•
Inductive load: 4A
•
Capacitive load: 1A
Exceeding these ratings will adversely affect the service life of the relay!
Dimensions:
57.1 x 39 x 21 mm
ZigBee Dynamic MESH
2.4 GHz
E: [email protected] T: +31(0) 252 43 30 70 W: www.plugwise.com
* Total max. current Stealth M and M+ : 20A.
All specifications without prejudice.