   Dingo Pup User Guide

Load Control Menu

Long push on LINT to enter 
the Load Control Menu:
LSET:  long  push  to  turn  the 
Load terminal ON or OFF.

In  Program  4,  more  Load 
Terminal 

control 

op-

tions  are    available  (LOFF, 
LON,LDEL), and more Load 
Function  options  are  avail-
able  in  the  MODE  menu. 
See the Dingo or Dingo Pup 
reference  manual  for  more 
information.

Generator Control

The  G  terminal  on  the  Pup 
is  controlled  by  the  Pup 
battery  voltage  in  Program 
0-3.  Long  push  on  CINT  to 
enter the Generator Control 
Menu:
GSET:  long  push  to  turn 
the  G  terminal  ON  or  OFF. 
Short push to advance to
GRUN:  long  push  to  adjust 
the 

generator 

exercise 

period  (default  1.0  hour). 
Short push to advance to
GDAY:  long  push  to  adjust 
the days between generator 
exercise  events  (default  0, 
not enabled).
In 

Program 

4, 

more 

Generator  Terminal  and 
Generator 

Function  

options  are  available.  See 
the  Dingo  or  Dingo  Pup 
reference  manual  for  more 
information.

Note  -  NEVER  connect 
batteries  or  inverters  to 
the  load  terminals  of  the 
controller.    They  will  cause 
heavy  current  flow  which 
may damage the controller.

Содержание Dingo Pup

Страница 1: ...DINGO PUP Negative Ground 20A Max Charge 20A Max Load Dingo Series Expansion Unit User Guide Read this before installing Ver 1 6 230317...

Страница 2: ...In a dry environment out of direct sunlight Away from flammable gases or liquids Away from spiders wasps or other insects which might make nests in it Pup configuration Each Pup must have its own add...

Страница 3: ...your Settings 10 What is a Dingo Pup The Dingo Pup is used to expand the capacity of the Dingo solar charge controller Up to 9 pups can be added to a system Each Pup is controlled by the Dingo The Din...

Страница 4: ...nals tightly in the order listed on page 6 Fig 1 Warning This controller is for DC current ONLY 638 BOOST Display Alarm LED Terminals for G and sensor wires plug in terminal block Accessory port Mount...

Страница 5: ...2 Test Solar Polarity 3 Connect Solar 4 Connect Load if required 5 Set Address and System Voltage 6 Connect the Pup to the Dingo Bus T BATTERY SOLAR BATTERY LOAD G Terminals Sensor T Temperature T B...

Страница 6: ...nnect the negative wire from the solar panel s to the solar panel negative terminal 27 8 BOOST V T Battery Display comes on Connect Battery 1 For safety most installation standards require fuses or ci...

Страница 7: ...f the load connection is being used connect the negative wire from the DC load circuit to the load negative terminal and the positive load wire to the load positive terminal Test the load circuit Chec...

Страница 8: ...es about one second Getting back Wherever you are in the menu system a series of short pushes will bring you back to the top level menus without changing any settings There are two exceptions when a n...

Страница 9: ...ush Thin arrow short push SET ADDR TIME VOLT PROG BCAP Set Set Set Set Set DATA VMAX VMIN FTIM SOC TEMP SOLV HIST History Data OUT INT Clear IN INT Clear LOAD LINT Low Battery Disconnect CHRG CINT Gen...

Страница 10: ...ss will start flashing c Short push until the address shown is correct If you reach 9 it will cycle back to 0 unset Choose the next address after any other Pups already in use d When the address is co...

Страница 11: ...t push until the voltage is correct for your battery If you pass 48V it will cycle back to 12V c When the voltage shown is correct long push to set it 4 Set the System Program Short push to move from...

Страница 12: ...on choose program 2 or 3 If you have connected lights to the load terminals they will switch on at dusk and switch off at dawn Low Battery Disconnect Program 0 1 To prevent battery damage due to overd...

Страница 13: ...age in Program 0 3 Long push on CINT to enter the Generator Control Menu GSET long push to turn the G terminal ON or OFF Short push to advance to GRUN long push to adjust the generator exercise period...

Страница 14: ...ontrol it should not be necessary to change the ESET SW setting Connecting the Pup to the Dingo If the program selection PROG on the Dingo is set in the range 0 through to 3 then the Dingo is automati...

Страница 15: ...Guide Battery 42 1 BOOST A T SOLAR ARRAY 1 DINGO 15 8 A T SOLAR ARRAY 2 PUP 1 17 8 A T SOLAR ARRAY 3 PUP 2 Additional Pups Battery Fuses are required for safety 3 way adaptor Dingo with Dingo Pup expa...

Страница 16: ...olt age If the load increases or the insolation reduces then Pups will be turned back on until a balance is restored The Expanded Dingo System The Pups report back their current to the Dingo which dis...

Страница 17: ...formation can be accessed via the Dingo External Battery Temperature Sensor DT or DTB Pup temperature input has no effect on battery charging when the Pup is part of a Dingo System The DT is a plastic...

Страница 18: ...id the battery reach VMAX shows today s maxi mum voltage since midnight VMIN shows today s minimum voltage Both are in the DATA sub menu The actual battery voltage is shown on the BATV screen What is...

Страница 19: ...MAX Maximum battery voltage since midnight VMIN Minimum battery voltage since midnight FTIM Time of day the controller entered the Float state if it didn t begin in float SOC This is not relevant to t...

Страница 20: ...on HIST will put you in history mode where you can cycle through each day s data In the history display DAY 1 is yesterday and DAY 99 is 99 days ago Thin arrow short push Thick arrow long push BATV CH...

Страница 21: ...d from our website www plasmatronics com au Independent Mode When the Pup is not under the control of a Dingo it operates as if it were a Dingo but with out the ability to have acces sories connected...

Страница 22: ...up eg for a 24V system multiply each voltage figure by 2 CHRG Setting for program number Parameter 0 1 2 3 GMOD 0 G ON V 11 5 GOFF V 13 8 GDEL Min 10 GEXD Day 30 GRUN Hr 1 0 LOAD Setting for program n...

Страница 23: ...B sense to BAT 30 V Max continuous charge current SOL 20 A Max continuous load current LOAD 20 A Max short term load current 5 minutes 30 A Max G relay current 300 mA Battery Temp sensor range 20 to 7...

Страница 24: ...Dingo Pup User Guide 24 Plasmatronics Pty Ltd 75 Newman St Thornbury 3071 Victoria Australia ph 61 3 94869902 info plasmatronics com au www plasmatronics com au...

Отзывы: