2. Tighten the wire-clamp screws for preventing the wires from loosening.
1
2
3
4
5
6
Power 1
Fault
Power 2
+
-
+
-
Note
1.
The wire gauge for the terminal block should be in the range
between 12 and 24 AWG.
2.
The DC power input range is 48V ~ 56V DC.
2.6 Wiring the Fault Alarm Contact
The fault alarm contacts are in the middle of the terminal block connector as the
picture shows below. Inserting the wires, the Industrial PoE+ Switch will detect
the fault status of the power failure and then forms an open circuit. The following
illustration shows an application example for wiring the fault alarm contacts.
Fault Alarm Contacts
The Fault Alarm Contacts are
energized (CLOSE) for normal
operation and will OPEN when
failure occurs
Fault
Insert the wires into the fault alarm contacts
Note
1.
The wire gauge for the terminal block should be in the range
between 12 and 24 AWG.
2.
Alarm relay circuit accepts up to 30V, max. 3A currents.