Table 1 

Fault 

Code 

Description 

Comments. Solution 

Overheating of 
the heat 
exchanger 

Check the intake and output of the heating unit for 
unobstructed entry and exit of heated air. 

Overheating in 
the area of the 
control unit. 
Flame indicator 
overheating 

Check the intake and output of the heating unit for 
unobstructed entry and exit of heated air. 

 

Check the combustion air supply system and the gas 
exhaust hose. 

 

Repeat the start-up to cool down the heater. 

12 

Disabling, 
overvoltage 

Check the battery, voltage regulator and the supply wiring. 
Voltage between the power connector contacts 1 and 2 
should be no higher than 30V. 
(for 12V products - no more than 16V). 

13 

Start-up attempts 
exhausted 

Check for the quantity and supply of fuel. Check the 
combustion air supply system and the gas exhaust hose. 

15 

Disabling, 
undervoltage 

Check the battery, voltage regulator and the supply wiring. 
Voltage between the power connector contacts 1 and 2 
should be not lower than 20V 
(for 12V products - not lower than 10V). 

16 

Exceeded time for 
ventilation 

Check the air supply system for combustion and the gas 
exhaust hose. 

20 

No connection 
between 
Controller and the 
control unit 

Check connecting cables, connectors. 

30 

Check connecting cables, connectors. 

29 

Exceeded 
permissible 
number of 
flameouts 

Check for the quantity and supply of fuel. 

 

Check the combustion air supply system and the gas 
exhaust hose. 

31* 

Overheating in 
the area of the 
temperature 
sensor at the hot 
air outlet 

Check the intake and output of the heating unit for 
unobstructed entry and exit of heated air. 

 

 

Содержание PU-16

Страница 1: ...Heater Controls Air Heaters PLANAR EN ...

Страница 2: ...oller during the heater operation After turning off the heater reconnection should be made at least after 5 10 seconds For safe operation of the heater after two consecutive failed start ups customer service should be contacted to identify and repair the malfunction The warranty period and conditions of the warranty service are listed on the warranty card Safety Risk of explosion in places where l...

Страница 3: ...at output ventilation mode ON OFF increasing the desired setting of temperature or heat output Application The functions of the Controller Manual Start up for unlimited time and Shutdown of the heater Selection of Heat Control Temperature Control operation mode Activation of Ventilation mode Indication of preset values for temperature or power Indication of 1 of the 3 Temperature Sensors installed...

Страница 4: ...on mode Operation of the heater in the Temperature Control Mode Cab sensor Sensor in the Controller Sensor in the heating unit Operation mode LED steady the heater is working blinks slowly the heater is not working blinks every 1 sec malfunction detected blinks fast the heater is shutting down ...

Страница 5: ...rature Control and incompatible with the Heat Control mode In Heat Control mode the heater will not stop its heating operation regardless of the middle LED display After each shutdown of the heater the activation of the Ventilation mode is reset When the Heat Control mode is selected the heater constantly operates at the preset level of heating power When a comfortable temperature is reached we re...

Страница 6: ...ion is terminated and air ventilation in the room begins When the room temperature falls to 5 C below the preset value the heater starts up again The heater can be switched off manually Operating Controller When the heater is connected to the vehicle electrical system the display shows the software version of the Controller Negative temperature is displayed with a minus sign navigating the main me...

Страница 7: ...e heater power shall NOT be disconnected until the end of the purging cycle To save energy a light indicator turns off in 20 seconds after the last press of any button To resume display press any button In case of open circuit failure of the cabin temperature sensor during operation the heater will go to medium power level Troubleshooting Faults that occur during heater operation are coded and aut...

Страница 8: ...empts exhausted Check for the quantity and supply of fuel Check the combustion air supply system and the gas exhaust hose 15 Disabling undervoltage Check the battery voltage regulator and the supply wiring Voltage between the power connector contacts 1 and 2 should be not lower than 20V for 12V products not lower than 10V 16 Exceeded time for ventilation Check the air supply system for combustion ...

Страница 9: ...center Alarm System Remote The operation of the heater can be controlled by a remote control of a security alarm system provided that it has a free channel Heater control can be carried out in two ways with short time closures of relay contacts closure time of 0 5 to 3 seconds and with a long time closure longer than 3 seconds With short closures the first pulse switches the heater ON the second O...

Страница 10: ...in harsh environments cold vibration etc Both the modem and the phone must have a SIM card installed Heater control is performed using a software application installed on the mobile phone see Instructions to the modem Operating parameters can be changed by means of SMS commands Changes are possible at any time For detailed instructions on working with the modem please see the User Guide for Teplos...

Отзывы: