DR08…Ax
F/I transmitter with analogue output
All turbine flowmeters of the DR08 series can be equipped with
an integrated F/I transmitter and thus provide an analogue signal
output 4...20 mA instead of the pulse output.
Technical Data:
Output signal:
4...20 mA
Accuracy (Output
signal):
± 1,25 % of measured value (plus
the respective accuracy of the
turbine flow sensor)
Current limitation:
approx. 26 mA
Scaling:
Different flow ranges, see order
code flow sensor
other scaling from 10 pieces
possible
Power supply:
18...30 VDC
Max. current
consumption:
30 mA
Max. burden:
250
Ω
against GND
Residual ripple:
0,2 mA (peak-to-peak) over the
entire range
Version:
3-wire, not galvanically isolated,
common GND of supply voltage
and output signal
Electrical connection:
4-pin plug, M12x1
Max. medium
temperature:
depending on the Tmax of the
flow sensor used, but max. 80 °C
Material of transmitter
housing:
plastic PA
Protection class:
IP54