User manual - PLE500 -
11
9
AI.0 offset calibration
10 AI.1 offset calibration
Offset calibration Value added to or taken from the process displayed.
-10000..+10000 [digit].
Default
0.
11 AI.0 gain calibration
12 AI.1 gain calibration
Gain calibration. Value to be multiplied by the process in order to calibrate on the operating point.
E.g.: to correct the 0..1000 operating scale that displays 0..1010, set the parameter to -1.0
-1000 (100.0%)...+1000 (+100.0%),
Default
: 0.0.
13 AI.0 latch-On function
14 AI.1 latch-On function
Function available from software version 2.00
15 AI.0 input filter
16 AI.1 input filter
Analog input reading filter: increases process stability. It indicates the number of samples to
average in the process calculation.
1...30. (
Default
: 10)
17 AO.0 type output
18 AO.1 type output
Selects the operating mode of the analog output.
0
4-20 mA (
Default
)
1
0-20 mA.
2
Proportional time (
available from software version 1.01
)
19 AO.0 output lower limit
20 AO.1 output lower limit
Continuous output range lower limit (value associated to 4mA / 0 mA).
-32767..+32767 [digit],
Default
: 0.
21 AO.0 output upper limit
22 AO.1 output upper limit
Continuous output range lower limit (value associated to 20 mA).
-32767..+32767 [digit],
Default
: 1000.
23 AO.0 output cycle time
24 AO.1 output cycle time
Determines the cycle time in managing the analog output in proportional time mode (
available
in software version 1.01
).
1..600 [s],
Default
: 10.
25 Digital input filter
Defines the time during which the digital input must remain stable before being considered valid.
0..250 [ms],
Default
: 5 ms.