- DRR227 -
User manual
12
G.caL.
Gain Calibration (Password 5678)
Value multiplied to the process value to calibrate the working point. Ex: to correct
the range from 0...1000°C showing 0...1010°C, set the parameter to -1.0.
-99.9%..+100.0%,
Default
: 0.0.
13
c. HY.
Command Hysteresis (Password 1234)
Hysteresis in ON/OFF
-999..+999 [digit1] (degrees.tenths for temperature sensors).
Default
0.2.
14
c. Ld.
Command Led (Password 5678)
State of the OUT1 led corresponding to the relevant contact
o.c.
ON with open contact
c.c.
ON with closed contact (
Default
)
15
c. S.e.
Command State Error (Password 5678)
State of contact for command output in case of error
o.c.
Open contact (
Default
)
c.c.
Closed contact
16
c. s.p.
Command Setpoint Protection (Password 1234)
Allows/denies modifications of command setpoint value
free
Modifiable by the user (
Default
)
Lock
Locked
17
c. re.
Command Reset (Password 5678)
Type of reset for command contact (always automatic in PID functioning)
are.
Automatic Reset
(
Default
)
mre.
Manual Reset
mre.s.
Manual Reset Stored
(keeps relay status also after an eventual power
failure)
18
c. de.
Command Delay (Password 5678)
Command delay (only in ON / OFF functioning).
-900..+900 seconds..
Default
: 0.
Negative: delay in switching off phase.
Positive: delay in activation phase.
19
au.ma.
Automatic / Manual (Password 1234)
Enables automatic/manual selection.
dis.
Disabled (
Default
)
En.
Enabled
En.St.
Enabled stored
Содержание DRR227